FLOOR CLEARANCES
The gas log heater must be installed at least 3/4" above
any combustible flooring material, such as carpeting or
tile, which is closer than 14" to the base of the fireplace.
The minimum distance must be maintained from the top
surface of carpeting, tile, etc. Figure 8
OR
The gas log heater may be installed nearer to the floor if a
minimum of 14" of noncombustible material such as slate
or marble is installed between the base of the fireplace and
the combustible flooring. Figure 9
Monessen • NBST27 Gas Log Set Installation/Owner's Manual • 81D3032 • Rev A • 08/16
Figure 9 -
Minimum Clearance above Combustible Flooring with Noncombus-
tible Material Installed at Base of Fireplace
FP2369
comb floor
NBST27 Unvented Gas Log Set
Figure 8 -
Minimum Clearance above Combustible Flooring
Heater in Fireplace
or Firebox
Combustible
Material
This distance may now
be less than 3/4"
14" Min.
Heater in Fireplace
or Firebox
Combustible
Material
3/4"
FP2368
combustible floor
9