IS/ISP SERIES
INTEGRATO SEQUENCER
DESCRIPTION
The Integrato Sequencer (IS & ISP) features integrated controls
intended for use with larger reverse pulse jet filter cleaning
systems. The IS & ISP have been designed to operate across a
wide range of environmental conditions. It is suitable for use with
all types of filters, including bags, cartridges, sintered metal or
ceramic filters.
The IS sequencer operates in continuous mode, whereas the ISP
has a built-in differential pressure sensor, allowing this sequencer
to be demand driven.
IS & ISP may be ordered as the sequencer only or in an enclosure
(polycarbonate).
FEATURES
Low temperature operation −40°C (−40°F)
Automatic valve detection.
Voltage-free coil error output and a visual indication on the
display showing which pilot valve output has an error, enabling
quick fault finding and debugging.
Controls up to 40 pilot valves. Each AC output can have 10 pilot
valves connected in parallel, enabling up to 400 pilot valves to be
supported. Each DC output can have 3 pilot valves connected in
parallel between −20°C to 60°C (−4°F to 140°F), enabling up to
120 pilot valves to be supported and 2 pilot valves connected in
parallel between −40°C to 60°C (−40°F to 140°F), enabling up to
80 pilot valves to be supported.
Conforms to the requirements of UL, CE, FCC and RCM.
TECHNICAL CHARACTERISTICS & PERFORMANCE
dP Support
0 to 4.5 kPa
Input Voltage
AC: 100/240 V @ 50/60 Hz
Output Voltage
AC: 100/240 V @ 50/60 Hz (same as input)
DC: 24 V
Maximum Input Power
AC IN, AC OUT Model: 225 W
AC IN, DC OUT Model: 65 W
Discrete Solenoid Outputs
12, 20 or 40 outputs
Enclosure
Polycarbonate or no enclosure
Protection Rating (Large
Polycarbonate: IP 66/67 & NEMA 1, 3, 3S,
Enclosure)
4, 4X, 6, 6P & 12
Protection Rating (Small
Polycarbonate: IP65 & NEMA 1, 4, 4X, 12
Enclosure)
& 13
−40°C to 60°C (−40°F to 140°F)
Operating Temperature
ON & OFF Time
ON: 30 ms to 1000 ms, OFF: 1 s to 1000 s
Inputs
Voltage Free: Fan Stop, Low Header Alarm
Outputs
Voltage Free: Coil Error.
Analogue Output: 4–20 mA dP signal on
the ISP
©COPYRIGHT Goyen Controls Co. Pty. Ltd.
PRODUCT INSTALLATION INSTRUCTIONS
CIRCUIT BOARD LAYOUT
ISP12
16
3
2
4
1
ISP40
4
16
3
4
1
2
1
AC Input Voltage: Electrical connection to the board. Active, Earth
and Neutral connections. Max. cable size 14–26 AWG.
2
ON:OFF Power Switch: Switch power the board ON and OFF.
3
Fuse (Over Current Protection): Replacement fuse T2.5 A 250 V
(slow blow).
4
Outputs Common Terminal: This is the common terminal for all
the 12 solenoid outputs. Max. cable size 12–22 AWG.
5
Discrete Solenoid Output Terminals: Connect each solenoid wire
to a separate output terminal. Max. cable size 12–22 AWG.
6
Coil Alarm Output (Voltage Free): This output triggers when the
coil fails to pulse correctly. It may indicate a fault with the coil or
wiring to that coil. Max cable size 14–26 AWG.
7
4–20 mA dP Output: This output mirrors the output of the built in
dP sensor in the form of a 4–20 mA signal. (ISP only)
8
Low Header Alarm Input (Voltage Free): This input allows for the
connection of a sensor to monitor the header tank pressure. In
the event the pressure drops below the preset level, the pulsing
cycle is paused. Max. cable size 14–26 AWG.
PAGE 1 of 24
GOYEN IS/ISP SERIES CONTROLLER
DEINE-012
ISSUE: 4
DATE: 04.05.2016
15
14
12
11
10
9
8
7
6
5
15
5
13
12
11
10
9
7
5
13
14
8
6

Advertisement

loading

Summary of Contents for Pentair Goyen IS Series

  • Page 1 PRODUCT INSTALLATION INSTRUCTIONS GOYEN IS/ISP SERIES CONTROLLER DEINE-012 ISSUE: 4 DATE: 04.05.2016 IS/ISP SERIES INTEGRATO SEQUENCER DESCRIPTION CIRCUIT BOARD LAYOUT ISP12 The Integrato Sequencer (IS & ISP) features integrated controls intended for use with larger reverse pulse jet filter cleaning systems.
  • Page 2: Product Installation Instructions

    PRODUCT INSTALLATION INSTRUCTIONS GOYEN IS/ISP SERIES CONTROLLER DEINE-012 Power/Reset Button: This is used to turn the controller Fan Stop Input (Voltage Free): This input is used to stop the controller remotely. It may be connected to the blower fan control ON and OFF and to conduct a Soft Reset.
  • Page 3 PRODUCT INSTALLATION INSTRUCTIONS GOYEN IS/ISP SERIES CONTROLLER DEINE-012 dP Units * Off Time Press Select Press Select when the ‘dP Units’ LED is lit. when the ‘Off Time’ LED is lit. This LED should start to flash indicating it is in programming mode. This LED should start to flash, indicating it is in programming mode.
  • Page 4 INSTRUCTIONS D'INSTALLATION DU PRODUIT CONTRÔLEUR DE SÉRIE GOYEN IS/ISP DEINE-012 VERSION : 4 DATE : 04/05/2016 SERIE IS/ISP SEQUENCEUR INTEGRATO DESCRIPTION CONFIGURATION DU CIRCUIT IMPRIME Le Séquenceur Integrato (IS et ISP) est doté de commandes ISP12 intégrées destinées à être utilisées avec des systèmes de nettoyage du filtre à...
  • Page 5: Instructions De Programmation

    INSTRUCTIONS D'INSTALLATION DU PRODUIT CONTRÔLEUR DE SÉRIE GOYEN IS/ISP DEINE-012 Touche alimentation/réinitialisation : permet de mettre Entrée Arrêt du ventilateur (hors tension) : Cette entrée est utilisée pour arrêter le séquenceur à distance. Il peut être en MARCHE ou d'ÉTEINDRE le contrôleur et de réaliser raccordé...
  • Page 6 INSTRUCTIONS D'INSTALLATION DU PRODUIT CONTRÔLEUR DE SÉRIE GOYEN IS/ISP DEINE-012 dP High = dP élevé * Off Time = Temps d'arrêt Appuyez sur Sélectionner lorsque le voyant LED « dP High » est Appuyez sur Sélectionner lorsque le voyant LED « Off Time » est allumé.

This manual is also suitable for:

Goyen isp series