10' (3 m)
OR LESS
2' (61 cm)
MINIMUM
** *** 6" (15.2 cm) MINIMUM
* 7' (2.1 m) ABOVE PUBLIC WALKWAYS
* 3' (91 cm) MIN. ABOVE AIR INTAKES WITH 10' (3 m) RADIUS
10' (3 m)
OR LESS
2' (61 cm)
MINIMUM
** *** 6" (15.2 cm) MINIMUM
* 7' (2.1 m) ABOVE PUBLIC WALKWAYS
* 3' (91 cm) MIN. ABOVE AIR INTAKES WITH 10' (3 m) RADIUS
* USE VERTICAL VENT PIPE TO MEET MINIMUM HEIGHT REQUIREMENTS
** MUST BE 4' (1.2 m) AWAY FROM ANY WINDOW, DOOR, OR GRAVITY AIR INLET
*** RECOMMENDED SERVICE CLEARANCES IS 24" (61 cm) FROM THE FRONT OF THE HEATER TO A WALL;
18" (45.7 cm) FROM THE WATER SIDE TO A WALL
12
3' (91 cm)
MINIMUM
9" (22.9 cm)
MINIMUM
-
1' (30.5 cm)
ABOVE GRADE
OR NORMAL
SNOW LINE
3' (91 cm)
MINIMUM
9" (22.9 cm)
MINIMUM
-
1' (30.5 cm)
ABOVE GRADE
OR NORMAL
SNOW LINE
Figure 24. Indoor Clearances
UNCONTROLLED DOCUMENT IF PRINTED
APPROVED
10' (3 m)
OR LESS
2' (61 cm)
MINIMUM
** ***12" (30.5 cm) MINIMUM
* 7' (2.1 m) ABOVE PUBLIC WALKWAYS
* 3' (91 cm) MIN. ABOVE AIR INTAKES WITH 10' (3 m) RADIUS
10' (3 m)
OR LESS
2' (61 cm)
MINIMUM
** *** 6" (15.2 cm) MINIMUM
* 7' (2.1 m) ABOVE PUBLIC WALKWAYS
* 3' (91 cm) MIN. ABOVE AIR INTAKES WITH 10' (3 m) RADIUS
3' (91 cm)
MINIMUM
9" (22.9 cm)
MINIMUM
-
1' (30.5 cm)
ABOVE GRADE
OR NORMAL
SNOW LINE
3' (91 cm)
MINIMUM
9" (22.9 cm)
MINIMUM
-
1' (30.5 cm)
ABOVE GRADE
OR NORMAL
SNOW LINE