Check point 3. Check the solenoid coil and 4-way valve
Solenoid coil
Remove P60 from PCB and check the resistance value of coil. Resistance value is about 2.085
kΩ (for 09 model) or 1.97 kΩ (for 12/18 models) (at 68 °F (20 °C)).
If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Check the voltage of 4-way valve
Check the voltage P60 of Main PCB.
Check if AC 198 V (AC 220 V -10%) to AC 264 V (AC 240 V +10%) appears at P60 of Main PCB.
Heating operation
If it is not voltage, Replace Main PCB.
Cooling operation
If it is voltage, Replace Main PCB.
Check point 5. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
2-27. E: 99. 4-way valve error (Outdoor unit)
End
- (03-33) -
2. Troubleshooting with error code