Service - Lennox ELITE Series Installation Instructions Manual

Gas furnace downflow air discharge
Table of Contents

Advertisement

The cool fan off delay (amount of time that the blower
operates after the cool demand has been satisfied) is 45
seconds and not adjustable.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.
HEAT FAN OFF TIME IN SECONDS
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
achieve desired setting.
60 Second
90 Second
off Time
off Time
Figure 56
Blower Speeds
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace.
2 - Remove blower access panel.
3 - Disconnect existing speed tap at integrated control
speed terminal.
NOTE - Termination of any unused motor leads must be
insulated.
4 - Place unused blower speed tap on integrated control
"PARK" terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
TABLE 19 on page 50 for allowable heating
speeds.
6 - Connect selected speed tap at integrated control
speed terminal.
7 - Re-secure blower access panel.
8 - Turn on electrical power to furnace.
9 - Recheck temperature rise.
Exhaust and Air Intake Pipe
1 - Check exhaust and air intake connections for
tightness and to make sure there is no blockage.
2 - Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check
termination for blockages.
3 - Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout
switches on burner box assembly if necessary.
120 Second
180 Second
off Time
off Time
Page 43

Service

WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place when
the blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply
with the Lennox Limited Warranty, your system should be
checked as follows:
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2- Check the condition of the belt and shaft bearings if
applicable.
3- Inspect all gas pipe and connections for leaks.
4- Check the cleanliness of filters and change if
necessary (monthly).
5- Check the condition and cleanliness of burners and
heat exchanger and clean if necessary.
6- Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor if
necessary.
7- Inspect the condensate drain and trap for leaks and
cracks. The drain and trap must also be cleaned
and the trap must be primed with water. Inspect the
rubber hoses connected to the pressure switches for
cracks or loose connections, replace as necessary.
Remove the rubber hoses from the cold end header
box and inspect for any blockage, clean as needed.
If strainers are installed in the hoses remember to
remove and clean before reinstalling the hoses.
8- Evaluate the heat exchanger integrity by inspecting
the heat exchanger per the AHRI heat exchanger
inspection procedure. This procedure can be viewed
at www.ahrinet.org
9- Ensure sufficient combustion air is available to the
furnace. Fresh air grilles and louvers (on the unit and
in the room where the furnace is installed) must be
properly sized, open and unobstructed to provide
combustion air.