Use Of Furnace As A Construction Heaterl - Lennox ELITE Series Installation Instructions Manual

Gas furnace downflow air discharge
Table of Contents

Advertisement

In the absence of local codes, units must be installed
according to the current National Fuel Gas Code (AN-
SI-Z223.1/NFPA 54). The National Fuel Gas Code is avail-
able from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA-B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
In order to ensure proper unit operation in non-direct vent
applications, combustion and ventilation air supply must
be provided according to the current National Fuel Gas
Code or CSA-B149 standard.
Locations and Clearances
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in figure 13. Accessibility and
service clearances must take precedence over fire protec-
tion clearances.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a
hazardous atmosphere, the furnace must be installed ac-
cording to recommended good practice requirements and
current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Fail-
ure to do so may cause erratic limit operation and prema-
ture heat exchanger failure.
This EL196DFE furnace must be installed so that its elec-
trical components are protected from water.
Installation in Combination with a Cooling Coil
When this furnace is used with cooling units (figure 3),
it shall be installed in parallel with, or on the upstream
side of, cooling units to avoid condensation in the heating
compartment. With a parallel flow arrangement, a damper
(or other means to control the flow of air) must adequately
prevent chilled air from entering the furnace. If the damper
is manually operated, it must be equipped to prevent op-
eration of either the heating or the cooling unit, unless it is
in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of
the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
GAS UNIT
Dampers
(open during heating
operation only)
NOTE - This furnace is designed for a minimum continu-
ous return air temperature of 60°F (16°C) or an intermittent
operation down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
The EL196DFE furnace may be installed in alcoves, clos-
ets, attics, basements, garages, utility rooms and crawl
spaces.
This furnace design has not been CSA certified for instal-
lation in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
Use of Furnace as Construction Heater
Units may be used for heating of buildings or structures
under construction, if the following conditions are met to
ensure proper operation:
DO NOT USE THE UNIT FOR CONSTRUCTION HEAT
UNLESS ALL OF THE FOLLOWING CRITERIA ARE
MET:
• Furnace must be in its final location. The vent system
must be permanently installed per these installation in-
structions.
• Furnace must be installed as a two pipe system and
one hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc-
tion.
• A room thermostat must control the furnace. The use
of fixed jumpers that will provide continuous heating is
prohibited.
• The input rate and temperature rise must be set per the
furnace rating plate.
• Supply and Return air ducts must be provided and
sealed to the furnace. Return air must be terminated
outside of the space where furnace is installed.
Page 4
AIR HANDLER
Dampers
(open during cooling
operation only)
Figure 3

Advertisement

Table of Contents
loading

Table of Contents