Bryant 580J D17 Service And Maintenance Instructions page 50

Gas heat packaged rooftop nominal 15 to 27.5 tons with puron r-410a refreigerant
Table of Contents

Advertisement

NOTE 1
RUN
NOTE 3
50HJ540573
ACTUATOR
ASSEMBLY
DIRECT DRIVE
ACTUATOR
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen
sor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
Demand Control
Ventilation (DCV)
(Free Cooling LED Off)
Below set
(DCV LED Off)
(Free Cooling LED On)
(Free Cooling LED Off)
Above set
(DCV LED On)
(Free Cooling LED On)
*
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
** Modulation is based on the supply‐air sensor signal.
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply‐air sensor signals, between minimum position and either maximum
position (DCV) or fully open (supply‐air signal).
††† Modulation is based on the greater of DCV and supply‐air sensor signals, between closed and either maximum position
(DCV) or fully open (supply‐air signal).
500 OHM
RESISTOR
Fig. 62 − EconoMi$er2 with 4 to 20 mA Control Wiring
Table 19 – EconoMi$er IV Input/Output Logic
INPUTS
Enthalpy*
Y1
Outdoor
Return
On
High
Low
On
Off
On
Low
High
On
Off
On
High
Low
On
Off
On
Low
High
On
Off
VIOLET
PINK
OAT SENSOR
4-20mA SIGNAL
Compressor
Y2
Stage
Stage
1
2
On
On
On
Off
On
Off
Minimum position
Off
Off
Off
On
On
Off
Modulating** (between min.
position and full‐open)
Off
Off
Off
Off
Off
Off
Minimum position
On
On
On
Modulating†† (between min.
position and DCV
Off
On
Off
Off
Off
Off
On
On
Off
Modulating***
Off
Off
Off
Off
Off
Off
50
BLACK
4
3
5
BLUE
2
8
6
7
RED
1
10
11
9
WHITE
12
ECONOMISER2 PLUG
OUTPUTS
N Terminal†
Occupied
Unoccupied
Damper
Modulating** (between
closed and full‐open)
Modulating†† (between
closed and DCV
maximum)
maximum)
Modulating†††
TRANSFORMER
GROUND
24 VAC
4-20 mA
TO J9 ON
PremierLink
BOARD
C08310
Closed
Closed