Supply Pressure Switch
The LP conversion kit includes a supply low pressure
switch. The switch contacts (from terminal C to terminal
NO [Normally Open]) will open the gas valve power
whenever the supply line pressure drops below the
setpoint. See Fig. 48 and Fig. 49. The switch,
HK02LB008, opens contacts on pressure "fail" at 7.2
±0.70 in. wg. Contacts close on pressure rise above 10.2
in. wg. If the low pressure remains open for 15 minutes
during a call for heat, the IGC circuit will initiate an
Ignition Fault (5 flashes) lockout. Reset of the low
pressure switch is automatic on rise in supply line
pressure. Reset of the IGC requires a recycle of unit
power after the low pressure switch has closed.
Limit Switch
Remove the blower access panel. The Limit Switch is
located on the fan deck for sideshot units and on the
vestibule plate for downshot units. SeeFig 48.
580J*D08 only
GAS VALVE
Fig. 48 − LP Low Pressure Switch (Installed)
W2
Fig. 49 − LP Supply Line Low Pressure Switch Wiring
This switch also prevents operation when the propane tank
level is low which can result in gas with a high
concentration of impurities, additives, and residues that
have settled to the bottom of the tank. Operation under
these conditions can cause harm to the heat exchanger
system. Contact your fuel supplier if this condition is
suspected.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the
heat exchanger:
Combustion−Air Blower
Clean periodically to assure proper airflow and heating
efficiency. Inspect the blower wheel every fall and
periodically during the heating season. For the first
heating season, inspect the blower wheel bi−monthly to
determine proper cleaning frequency.
To access the burner section, open the heater access door
below the indoor fan panel.
C08238
To inspect the blower wheel, shine a flashlight into the
draft hood opening. If cleaning is required, remove the
motor and wheel as follows:
LP LOW PRESSURE
SWITCH
C08238A
39
LP LPS
IGC
BRN
C
J2-11
IGC
J2-12
TSTAT
PNK
1. Remove the combustion blower wheel and motor as-
sembly according to directions in the Combustion−
Air Blower section. See Fig. 50.
2. Remove the flue cover to inspect the heat exchanger.
3. Clean all surfaces as required using a wire brush.
1. Remove the seven screws attaching the induced−draft
motor housing to the vestibule plate. See Fig. 50.
2. The blower wheel can be cleaned at this point. If ad-
ditional cleaning is required, continue with Steps 3
through 5.
3. Remove the blower from the motor shaft by loosening
two setscrews.
4. Remove the motor by removing the four screws that
hold the motor to the mounting plate. Remove the
motor cooling fan by removing one setscrew.
5. Remove the nuts that hold the motor to the mounting
plate.
6. To reinstall, reverse the procedure outlined above.
BRN
NO
C
MGV
GRA
C08285