4-3-16 Full current error / PFC over-current error (Error Code : E462, E484)

1. Test items
1) Check the power connection. / Check the restart after power reset.
2) Install outdoor unit and check environment.
→ Check for wire disconnection related to outdoor unit Inverter PCB and check the installation environment.
3) Check the indoor unit installation environment.
4) Check the opening of service valve.
2. Check procedure
Power on 30 seconds after power off.
Is the outdoor unit installed properly?
Is the indoor unit installed properly?
Is service valve fully opened?
Is compressor running properly?
After replacing the Inverter PCB of the outdoor unit,
check for normal startup. → End the service.
Samsung Electronics
Yes
Yes
Yes
Yes
Outdoor unit installation and environment
check. → Check for normal operation at
restart. → End the service.
1. Check for wire disconnection related to
No
outdoor unit Inverter PCB.
2. Remove obstacle on the inlet of outdoor
unit and secure the space.
3. Remove obstacle on the outlet of outdoor
unit and secure the space.
Check installation environment of indoor
unit. → check for normal operation at
restart. → End the service.
No
1. Remove obstacle on the inlet and secure
the space.
2. Remove obstacle on the outlet and
secure the space.
No
No
Replace the compressor.
Troubleshooting
Open the valve.