1. Safety
Assembly and installation should only be carried
out by a qualified electrician, somebody who has
completed appropriate professional training and
has the knowledge and experience necessary to be
able to recognise and avoid the potential dangers
posed by electricity.
Before assembly/dismounting, disconnect the
power supply and ensure that the parts are no
longer live.
Prior to commissioning and using the product,
read and observe all the operating instructions.
The astronomical time switch corresponds to type 1
BSTU in accordance with IEC/EN 60730-2-7
Power reserve (6 years) is reduced when Bluetooth
OBELISK top3 is connected (in battery mode)
2. Proper use
Digital astronomical time switch with weekly program
and annual program
3 special programs with date function per channel
Interface for Bluetooth OBELISK top3
Programming by app possible
The astronomical time switch is intended for time-
controlled and manual switching of lights, fans etc.
Only for use in closed, dry rooms
The astronomical time switch is designed for wall
mounting (flush-mounting) in an interior switch range
3. Installation and connection
Flush-mounted installation
L With a standard flush-mounting box (see illustration).
L Observe the recommended installation height of
0.8 m–1.2 m!
Disconnect power source.
Connect the time switch according to the wiring diagram.
Screw down the time switch in the flush-mounted box .
Position the bezel frame on the time switch .
309713
2
N
L1
L1'
!
Secure device with an upstream type B or type C circuit
breaker (EN 60898-1) with a maximum of 10.
Connecting the cable
Strip cable to 8 mm (max. 9).
Insert cable in the open DuoFix plug-in terminal at 45°.
L 2 cables per terminal position possible.
To open the DuoFix plug-in terminal, press screwdriver
downwards.
Disconnecting the cable
Use the screwdriver to push the spring plug-in terminal
downwards.
4. Device description
Ø 60 mm
1
L
L
L1
N
45°
Spring plug-in
terminal opener
Bezel frame
Right/left buttons (configured as pre-selection)
Display
4 buttons to select the
functions
Bluetooth OBELISK top3
(9070130)
≥ 40 mm
1

Advertisement

Table of Contents
loading

Summary of Contents for Theben SELEKTA 070 top3 UP

  • Page 1 309713 Ø 60 mm Astronomical time switch SELEKTA 070 top3 UP 0700130 ≥ 40 mm 1. Safety Assembly and installation should only be carried out by a qualified electrician, somebody who has completed appropriate professional training and has the knowledge and experience necessary to be able to recognise and avoid the potential dangers posed by electricity.
  • Page 2: Display And Buttons

    Display and buttons Overview of navigation menu MENU Programmed ON Display of times sunrise/ ASTRO PROGRAM TIME/DATE sunset Date display Time display ASTRO STANDARD TIME Channel status TIMES SPECIAL 1 SET DATE Weekday from TOTAL ASTRO PROG SIMULATION SU-WI 1–7 SPECIAL 2 ON OFFSET WEEK DAY...
  • Page 3: Initial Operation

    Initial operation ASTRO menu In the ASTRO menu, astro times, total simulation, offset, astro MENU mode and position (locations) can be queried or changed. • Astro times GERMAN COUNTRY Display of the astro times (including the offset) for the ENGLISH COORDINATES current day.
  • Page 4 Changing the astro time/location MENU ASTRO ASTRO TIMES MENU TOTAL SIMULATION ASTRO ASTRO TIMES OFFSET TOTAL ASTRO SIMULATION MODE ASTRO TIME OFFSET SUNSET ASTROMODE TWILIGHT ASTRO TIME DARKNESS LOCATION COUNTRY COORDINATES Press MENU. † Select ASTRO and press OK to confirm. †...
  • Page 5 Setting a fixed switching time (e.g. in standard L The public holiday set is set via app, or OBELISK software. program) L 24:00 is programmed as 00:00 of the following day. Holidays depending MENU on Easter in Germany PROGRAM STANDARD FREE 84 Holiday days before/after...
  • Page 6: Setting Holiday Function

    Enter YEAR, MONTH, DAY, HOUR, confirm with OK. † confirm. Activating PIN code The PIN code is set in OPTIONS via the menu. L If you have forgotten your PIN, please call the Theben Hotline. L Have the serial number of the device ready!
  • Page 7: Setting Manual Control Or Permanent Switching

    MENU OPTIONS OPERATING HOUR ILLUMINATION LANGUAGE NO PIN FACTORY WITH PIN CURRENT PIN SETTING NEW PIN INFO 00:00 Copy OBELISK → TIME SWITCH This copies the switch programme and optionally all time switch settings (e.g. time format, etc.) from the memory card to the time switch.
  • Page 8: Technical Data

    6. Technical data Operating voltage: 230 V AC, +10% / –15% Frequency: 50 Hz Standby: 0.4 W Max. switching capacity: 10 A (at 250 V AC, cos ϕ = 1) Switching capacity: 2 A (at 250 V AC, cos ϕ = 0.6) Min.