Lennox MERIT Series Installation Instructions Manual page 19

Downflow air discharge
Table of Contents

Advertisement

Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent
length calculation.
2" Pipe
Number
Model
Of 90°
Elbows
045
070
1
71
56
2
66
51
3
61
46
4
56
41
5
51
36
6
46
31
7
41
26
8
36
21
9
31
16
10
26
11
2" Pipe
Number
Model
Of 90°
Elbows
045
070
1
71
56
2
66
51
3
61
46
4
56
41
5
51
36
6
46
31
7
41
26
8
36
21
9
31
16
10
26
11
Attic or Crawl Space For Intake Air in Feet
Standard Termination at Elevation 0 - 4500 ft
090
110
045
34
14
115
29
9
110
24
4
105
19
100
14
95
9
90
4
n/a
85
80
n/a
75
70
Standard Termination Elevation 4500 - 10,000 f
090
110
045
34
100
29
95
24
90
19
85
14
80
n/a
9
75
4
70
65
n/a
60
55
TABLE 8
2-1/2" Pipe
Model
070
090
110
100
78
43
95
73
38
90
68
33
85
63
28
80
58
23
75
53
18
70
48
13
65
43
8
60
38
3
55
33
n/a
2-1/2" Pipe
Model
070
090
110
100
78
43
95
73
38
90
68
33
85
63
28
80
58
23
75
53
18
70
48
13
65
43
8
60
38
3
55
33
n/a
Page 19
3" Pipe
Model
045
070
090
118
117
98
113
112
93
108
107
88
103
102
83
98
97
78
93
92
73
88
87
68
83
82
63
78
77
58
73
72
53
t
3" Pipe
Model
045
070
090
118
117
98
113
112
93
108
107
88
103
102
83
98
97
78
93
92
73
88
87
68
83
82
63
78
77
58
73
72
53
110
98
93
88
83
78
73
68
63
58
53
110
98
93
88
83
78
73
68
63
58
53