Indoor Unit; Specifications - Mitsubishi Electric PFAV-P250VM-E Data Book

Air conditioning systems
Hide thumbs Also See for PFAV-P250VM-E:
Table of Contents

Advertisement

! ! . Indoor Unit

1. Specifications

(1) Standard type
Model Name
System capacity
System Power input
System current
Power source
Power input
Current
Type x Quantity
Airflow rate
Fan
External static pressure Pa
Motor output
Refrigerant
External finish
External dimension
Protection devices
Refrigerant
Liquid pipe
piping diameter
Gas pipe
Refrigerant piping allowable length m
Sound pressure level
Heat exchanger
Air filter
Net weight
Operating
temperature range
1. Cooling / Heating capacity indicates the value at operation under the following conditions.
(Cooling) Indoor: 27degCDB / 19degCWB, Outdoor: 35degCDB
(Heating) Indoor: 20degCDB, Outdoor: 7degDB / 6degCWB
Pipe length: 7.5m, Height difference: 0m
2. The sound pressure level is measured in an anechoic room.
Note
3. Long period operation in a high temperature and humidity atmosphere (dew point of 23˚C or more) may cause
condensation to form in the indoor unit.
Works not included: Installation / foundation work, electric connection work, duct work, insulation work,
the power source switch and other items are not specified in the specifications.
Indoor
PFAV-P250VM-E
PUHY-P250YHM-A
Outdoor
Cooling
kW
25.0 (Maximum28.0)
28.0 (Maximum 31.5)
Heating
kW
Cooling
kW
Heating
kW
Cooling
14.5-13.8-13.3 / 13.4-12.8-12.3
A
Heating
A
15.8-15.0-14.4 / 14.7-14.0-13.4
kW
A
3.4-3.2-3.1 / 2.3-2.2-2.1
Sirocco fan x 2
3
m /min
kW
mm
1748(H) x 1200(W) x 485(D)
Fan
Over current protection
mm
9.52 Brazed (12.7 for over 90m)
mm
22.2 Brazed
dB(A)
kg
Cooling
Heating
PFAV-P500VM-E
PUHY-P500YSHM-A
(PUHY-P250YHM-A x 2,
CMY-Y100VBK2)
50.0 (Maximum56.0)
56.0 (Maximum 63.0)
7.46 / 7.53
8.27 / 8.34
32.3-30.7-29.6 / 32.6-31.0-29.9
30.8-29.3-28.2 / 31.1-29.6-28.5
3-phase 4-wire 380-400-415V (50Hz / 60Hz)
0.82 / 0.89
6.2-5.9-5.7 / 6.5-6.2-6.0
Sirocco fan x 1
90
30 / 90
2.2
R410A
Galvanized steel plate (with polyester coating)
MUNSELL 5Y 8 / 1 or similar
1899(H) x 1420(W) x 635(D)
Over current protection
165
55
Cross fin (aluminum plate fin and copper tube)
Synthetic fiber unwoven cloth filter
156
Indoor: 10 to 25 degCWB
(Outdoor: -5 to 43 degCDB)
Indoor: 15 to 28 degCDB
(Outdoor: -20 to 15.5 degCWB)
5
PFAV-P750VM-E
PUHY-P750YSHM-A
(PUHY-P350YHM-A +
PUHY-P400YHM-A,
CMY-Y200VBK2)
71.0 (Maximum 80.0)
80.0 (Maximum 90.0)
17.85 / 18.84
17.00 / 17.99
48.1-45.7-44.1 / 47.5-45.1-43.5
43.4-41.2-39.8 / 42.8-40.6-39.2
2.37 / 3.36
10.9-10.4-10.0 / 10.3-9.8-9.4
180
30 / 130
5.5
R410A
1860(H) x 1750(W) x 1064(D)
Over current protection
15.88 Brazed
28.58 Brazed
165
59 / 62
PP Honeycomb fabric filter
265
26.33 / 27.40
23.93 / 25.00
4.30 / 5.37
Sirocco fan x 1
260
100 / 310
7.5
R410A
19.05 Brazed
34.93 Brazed
165
65
459

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents