Siemens RWF55.5 User Manual page 48

Compact universal controllers
Table of Contents

Advertisement

Parameter
Display
Outside temperature
Curve point 1 ¹
Boiler temperature
Curve point 1 ¹
Outside temperature
Curve point 2 ¹
Boiler temperature
Curve point 2 ¹
48/93
Building Technologies Division
Infrastructure & Cities Sector
Value range
-40...120
At1
SPL...SPH
Ht1
-40...120
At2
SPL...SPH
Ht2
¹
Setting of decimal place has an impact on this parameter
Note!
When using the RWF55... as a modulating controller only, or as a modulating
controller without the burner release function (1P, 1N), parameter HYS1 must be set to
0 and parameters HYS2 and HYS3 must be set to their maximum values.
Otherwise, for example, when using default parameter HYS1 (factory setting -5), the 3-
position controller is only released when the control deviation reaches -5 K.
User Manual RWF55...
7 Parameterization PArA
Factory
Remarks
setting
-10
Reference!
See chapter 5.5 Weather-compensated
setpoint shifting
60
Reference!
See chapter 5.5 Weather-compensated
setpoint shifting
20
Reference!
See chapter 5.5 Weather-compensated
setpoint shifting
50
Reference!
See chapter 5.5 Weather-compensated
setpoint shifting
CC1U7867en
05.11.2013