System Layout - Viessmann Vitodens 200-W B2HA 88 Technical Data Manual

Gas-fired wall-mounted condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 88:
Table of Contents

Advertisement

Installation Examples

System Layout 1

Vitodens 200-W, B2HA with a direct-connected heating circuit
Legend
A Vitodens 200-W B2HA boiler with
Vitotronic 200, HO1B outdoor reset control
B Outdoor temperature sensor !
C Vitotrol remote (optional)
D Heating circuit
E Heating circuit pump
F DHW circulating pump sA
G DHW storage tank
H DHW tank temperature sensor %
I Expansion tank
J Flow check valve
K DHW recirculation pump
L Temperature and pressure relief valve
M Pressure relief valve
*
Function based on coding of address 53
36
20
*
28/20
Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
Installation of ...
radiator heating circuit (high-temp. circuit)
DHW production
... with the following flow conditions:
The flow rate of the heating circuit is less than the
maximum possible water flow rate of the Vitodens 200-W
B2HA boiler (see page 9 for maximum water flow rate of
boiler).
The use of a low-loss header is strongly recommended if
the maximum water flow rate in the application concerned
exceeds the values shown in the applicable table on page
10, or if the system flow rates are unknown.
The low-loss header is available as accessory part.
See following pages for installation examples with a low-
loss header.
IMPORTANT
DHW circulating pump F must pump into the Vitodens
200-W boiler (as illustrated).