Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
Boiler Stand for B2HA 88, 100, 311, 352
Boiler Stand for B2HA 112, 150, 399, 530
(continued)
1. Remove the external accessories connection box
cover.
2. Loosen the screws at the bottom of the boiler
(do not remove completely).
3. Remove the front encloser panel (lift up and pull
away from the boiler).
4. Mount boiler onto the mounting bracket and ensure
the boiler is securely mounted. Then install the
holding bracket to the frame on top of the boiler.
5. Adjust the levelling screws to ensure the boiler
is level.
6. Connect the boiler to the installation fittings.
CAUTION
The boiler must be level both vertically and horizontally
to ensure proper draining of the condensate.
The boiler stand is used for free-standing installation of
a single boiler within the mechanical room.
When using the boiler stand, ensure that the stand is
securely fastened to the floor (recommended concrete
expansion anchors are Hilti model KB-TZ e x 4 or
equivalent.
Boiler Mounting