Boiler Control

Design and Function

Functions
Weather-compensated control of the boiler water
and/or supply temperature
Control of one heating circuit without mixer and two
heating circuits with mixer
Electronic maximum and minimum temperature limit
Demand-dependent heating circuit pump and burner
off control
Adjustment of a variable heating limit
Anti-seizing pump protection
Heating system frost protection
Integral diagnostic system
Maintenance display
DHW heating with priority
Control of solar DHW heating and central heating
backup in conjunction with the solar control module,
type SM1
Display of the solar energy yield
Auxiliary function for DHW heating (short-term
heating to a higher temperature)
External starting and blocking (in conjunction with
extension EA1)
To reduce the heat-up output, the reduced room
temperature will be raised in case of low outside
temperatures. The supply temperature will be raised for
a limited time to reduce the heat-up time after a setback
phase.
Control characteristics
PI characteristics with modulating output.
Time switch
Digital time switch (integrated into the programming unit)
Individual day and seven-day program
Automatic summer/wintertime changeover
Automatic function for DHW heating and DHW
recirculation pump
Time, day and standard switching times for central
heating, DHW heating and the DHW recirculation
pump are factory-set
Switching times are individually programmable,
i.e. up to four switching periods per day
Shortest switching interval:................... 10 minutes
Power reserve: .........................................14 days
26
Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
Setting the operating programs
The heating system frost protection (see frost protection
function) applies to all heating programs.
The following heating programs can be selected:
Zone circuits
Heating and DHW
Only DHW
Standby mode
External heating program changeover in conjunction
with EA1 extension.
Frost protection function
The frost protection function will be started when the
outside temperature drops below approx. 34°F (1°C).
With the frost protection function, the heating circuit
pump will be switched ON and the boiler water is
maintained at a lower temperature of approximately
68°F (20°C). The DHW tank will be heated to
approximately 68°F (20°C).
The frost protection function will be stopped when
the outside temperature rises above approximately
37°F (3°C) (default settings).
Summer Operation
Heating program "w"
The burner is only activated upon a call for domestic hot
water from the DHW storage tank (controlled by DHW
tank temperature sensor).