Dimensions And Weight; Connections - Carrier 42PQV...S Installation Manual

Table of Contents

Advertisement

42PQV...S/38VBH...S

Dimensions and weight

B
C
Table II : Connections
Minimum nominal thickness
Pipe diameter
inches-mm
1/4"-6,35
3/8"-9,52
1/2"-12,70
A
A
E
D
E
Ø 8,3
Outdoor unit
Indoor unit
Height difference
Minimum nominal
thickness(mm)
0,80
0,80
0,80
C
B
8,3
F
Model
Max.height difference
Max.pipe length
Pipe diameter
Model
Gas
(Suction)
009
9.52
012
12.7
All fittings are flare type.
Use only refrigeration grade pipes, (Cu DHP type according
to ISO 1337), seamless, degreased, deoxidized and
suitable for operating pressures of at least 4200 kPa and
with a burst pressure of 20700kPa.
Under no circumstances must sanitary type copper pipe
be used.
E N G L I S H
Mod.
42PQV...S
A
mm
790
B
mm
260
C
mm
196
kg
8.6
38VBH...S
Mod.
009 / 012
A
mm
750
B
mm
590
C
mm
280
D
mm
470
E
mm
140
F
mm
310
kg
33 - 37
009
012
8
10
Pipe diameter
Liquid
Gas
Liquid
(Liquid)
(Suction)
(Liquid)
mm
inches
6.35
3/8"
6.35
1/2"
10
15
1/4"
1/4"
GB - 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

38vbh...s

Table of Contents