Carrier 40VU007-0182-7G-QEE Installation And Owner's Manual page 26

Two-way cassette
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 6
Electrical Wiring
(B) Definition and description of SW03
SW03_1
Address setting
mode
Code-set indoor
SW03_2
unit address and
~
centralized
controller
SW03_8
address (Note 2)
Note 2:
•Set the address by code when connecting the centralized controller or gateway or charge system.
•Address of centralized controller =communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller =communication address+0=communication address
SW03_ 2=ON, address of centralized controller=communication address+64 (applies when centralized
controller is used and there are more than 64 indoor units)
•To use with 19848199886 in use, it is required to use code for address setting. Set SW03_1=ON and SW03_
2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are
address codes which are set according to actual address.
•Address setting function of wired controller is disabled.
(C) Definition and description of SW08
26°C Lock function Activation:
Default: Deactivated
Activation: Press "Health" button on remote controller 8 times in 5 seconds, and you hear 4 times beep, then
activate the function.
Deactivation: Press "Health" button on remote controller 8 times in 5 seconds, and you hear 2 times beep, then
deactivate the function.
[1]
0
1
[2]
[3]
[4]
[5]
[6]
[7]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
...
0
1
1
1
1
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
...
...
...
...
... ... ...
1
1
1
1
1
20
Address setting mode
Automatic setting (default)
Code-set address
[8] Address of indoor unit
0
0
0# (Default)
0
1
1#
1
0
2#
...
...
...
1
1
63#
0
0
0#
0
1
1#
1
0
2#
...
1
1
63#
Address of centralized
controller
0# (Default)
1#
2#
...
63#
64#
65#
66#
...
127#

Advertisement

Table of Contents
loading

Table of Contents