Outer Panels / Fan Motor

1. Outer Panels / Fan Motor
Warning
Step
1. Remove the outer panels.
Remove the screw of
1
the stop valve cover.
2
Pull down the stop
valve cover and remove
it.
3
Remove the 3 screws
and lift the top panel.
Remove the drip proof
4
plate.
2
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Drip proof plate
Stop
valve
cover
(R3237)
Shield plate
Hook
(R17312)
Top panel
(R19325)
Si001266EA
Points
The stop valve cover is
united with the shield plate.
When reassembling, make
sure to fit the 5 hooks.