Trane TCONT900AC43UA Installer's Manual page 14

Hide thumbs Also See for TCONT900AC43UA:
Table of Contents

Advertisement

TCONT900AC43UA
Selection
Minimum
Compressor On Time
Clock Format
Extended Fan On
Time Heat
Compressor Heat
Blower Off Delay
Profile
Extended Fan on
time control
Compressor Cool
Blower Off Delay
Profile
Compressor Heat
Fan On Delay Profile
Compressor Cool
Fan On Delay Profile
Keypad Lockout
Temperature Control
in Heat
Pub. No. 18-HD32D1-2
69-2079—05
Table 4. Installer Setup Menu
Installer Setup
Factory
Number (ISU)
Setting
0630
3
0640
12
0650
0
0651
5
0660
90
0661
5
0665
0
0667
0
0670
0
0680
2
Choices
Option
Description
0 - 15
Minimum number of
minutes compressor is on.
12, 24
12 - 12-hour clock format
24 - 24-hour clock format
0, 30, 60,
Fan operation is extended
90 or 120
0, 30, 60, 90 or 120
seconds after call for heat
ends.
0 - 5
0 - Disabled
1 - 0.5 min @ 35%
2 - 0.5 min @ 50%
3 - 1.5 min @ 50%
4 - 0.75 min @ 100%
5 - 1.5 min @ 100%
0, 30, 60,
Fan operation is extended
90 or 120
0, 30, 60, 90 or 120
seconds after call for cool
ends.
0 - 5
0 - Disabled
1 - 0.5 min @ 35%
2 - 0.5 min @ 50%
3 - 1.5 min @ 50%
4 - 0.75 min @ 100%
5 - 1.5 min @ 100%
0, 1, 5,
0 - Disabled
10, 20,
1 - Enabled - 50% for 1
30
minute (V.S. only)
5 - 5 seconds
10 - 10 seconds
20 - 20 seconds
30 - 30 seconds
0, 1, 5,
0 - Disabled
10, 20,
1 - Enabled - 50% for 1
30
minute (V.S. only)
5 - 5 seconds
10 - 10 seconds
20 - 20 seconds
30 - 30 seconds
0, 1, 2
0 - Unlocked keypad
1 - Partially locked keypad
2 - Fully locked keypad
1, 2, 3
1 - Less aggressive
temperature control (could
cause temperature
undershoot)
2 - Standard temperature
control in heating
3 - More aggressive
temperature control (could
cause temperature
overshoot)
14
Comments
Only shown for nonvariable
speed indoor units.
Only shown for variable
speed indoor units.
Only shown for nonvariable
speed indoor units.
Only shown for variable
speed indoor units.
For Variable Speed indoor
units: choices are 0 and 1.
For Non-variable Speed
indoor units: choices are 0,
5, 10, 20, and 30.
For Variable Speed indoor
units: choices are 0 and 1.
For Non-variable Speed
indoor units: choices are 0,
5, 10, 20, and 30.
Unlocked - all functions are
available.
Partially locked - only
temperature up and down
keys and ability to enter and
modify installer setup mode
are available.
Fully locked - only ability to
enter and modify installer
setup mode are available.
Applies to recovery ramp
and use of auxiliary heat
during recovery.