Cubicle Structure And Dimensions - Toshiba T300BMV2 Instruction Manual

Adjustable speed motor drive
Table of Contents

Advertisement

Cubicle Structure and Dimensions

The equipment is made up of one or more cabinets containing the transformer, incoming terminals,
converter section, and the inverter section. All components can all be accessed from the front.
This outline is for the standard Frame 1 model. For details of this and other ratings, see the outline
drawing of each product.
ADJUSTABLE SPEED
MOTOR DRIVE
Dimensional Outline of 4160V- (See the following page for dimensions)
General structure
1) All cubicles have a structure that allows maintenance from the front. Rear maintenance access is
not required. The cubicles may be placed within 1" of the rear wall.
2) Provide a maintenance space of at least 72 inches (1829 mm) in front of the cubicles.
3) Provide a clearance of at least 24 inches (610 mm) above the exhaust fans.
4) The following are not included in the dimensions on the next page:
a) Handle projections
b) Door mounted device projections
c) Fastener projections
IF08CZ9 September, 2019
Toshiba Reference File #328
MEDIUM VOLTAGE
LOCAL /
ESC
REMOTE
RUN
1
MODE
STOP
- 21 -