General Cubicle Structure
The configuration and dimensions of the equipment are described below.
Cubicle Structure and Dimensions
The equipment is made up of one or more cabinets containing the transformer, incoming terminals,
converter section, and the inverter section. All components can all be accessed from the front.
This outline is for the standard Frame 1 model. For details of this and other ratings, see the outline
drawing of each product.
ADJUSTABLE SPEED
MOTOR DRIVE
Dimensional Outline of 4160V- Frame 1 Cubicle (See the following page for dimensions)
General structure
1) Indoor cubicles have a structure that allows maintenance from the front. Rear maintenance
access is not required. The cubicles may be placed within 1" of the rear wall. (T300MV2) Refer to
the outline drawings for the MTX series as this varies with the frame size.
2) Provide a maintenance space of at least 72 inches (1829 mm) in front of the cubicles.
3) Provide a clearance of at least 24 inches (610 mm) above the exhaust fans. (T300MV2)
4) The following are not included in the dimensions on the next page:
a) Handle projections
b) Door mounted device projections
c) Fastener projections
IF08CZ10 April, 2019
MEDIUM VOLTAGE
REMOTE
LOCAL /
ESC
RUN
MODE
STOP
1