Installation
(cont.)
Braze or press fit the copper pipes in the solar cir-
cuit.
Soft solder could be weakened, particularly near the
collectors, due to the high temperatures that occur
there. Metal seal connections, locking ring fittings or
Viessmann plug-in connections with double O-rings
are the most suitable.
If other seals such as flat gaskets are used, ade-
quate glycol, pressure and temperature stability must
be guaranteed by the manufacturer.
Design all connections to be resistant to pressure
and temperature (observe the maximum stagnation
temperature of the collector).
Never use:
Teflon (inadequate glycol resistance)
Hemp connections (insufficiently gas-tight)
L
U
R
M
S
Fig. 14
Solar-Divicon
A
Shut-off valves
B
Non-return valves
C
Solar circuit pump
D
Air separator
E
Shut-off valve (adjusting screw above flow indica-
F
tor
)
H
G
Drain valve
Flow indicator
H

Commissioning

"Vitosol-F/-FM" service instructions.
T
A
P
K
B
B
L
C
C
D
F
G
E
H
M
Equip the system to EN 12975 or EN ISO 9806 with
an expansion vessel, safety valve and circulation
pump.
The expansion vessel must be approved to DIN
4807.
The diaphragms and seals of the expansion vessel
and safety valve must be suitable for the heat trans-
fer medium.
To calculate the pre-charge pressure, see the
"Vitosol" service instructions.
For operation without a Solar-Divicon, use only
safety valves that meet the following conditions:
Designed for 120 °C and up to 6 bar (0.6 MPa)
Letter ID "S" (solar) in the component identification
O
N
Fill valve
K
Stagnation heat sink
L
Expansion vessel
M
Drip pan
N
Collector
O
DHW cylinder
R
Cylinder temperature sensor
S
Collector temperature sensor
T
Solar control unit
U
15