Commands and Responses for the Support Board
Main code
11: Parameter error
20: Read not possible
144
Sub-
Probable cause
code
01
A correct memory area code has not
been used or Extended Data Memory
is not available.
02
The access size specified in the
command is wrong, or the first
address is an odd number.
03
The first address is in an inaccessible
area.
04
The end of specified word range
exceeds the acceptable range.
06
A non-existent program no. has been
specified.
09
The sizes of data items in the
command block are wrong.
0A
The IOM break function cannot be
executed because it is already being
executed.
0B
The response block is longer than the
max. permissible length.
0C
An incorrect parameter code has been
specified.
02
The data is protected.
An attempt was made to download a
file that is being uploaded.
03
The registered table does not exist or
is incorrect.
Too many files open.
04
The corresponding search data does
not exist.
05
A non-existing program no. has been
specified.
06
A non-existing file has been specified.
07
A verification error has occurred.
Check the command's memory area code
and set the appropriate code.
Set the correct access size for the
command.
Set a first address that is in an accessible
area.
Check the acceptable limits of the data
area and set the word range within the
limits.
Check the data link tables to be sure the
limit to link words has not been exceeded.
Check the program number and be sure
that it is set correctly.
Check the command data and be sure that
g
the sixes of the data items are correct.
Check the data link tables to be sure all
nodes in the refresh parameters are in the
common link parameters.
Either abort the current IOM break function
processing, or wait until it is completed and
execute the command.
Check the data link tables for node
addresses that have been set twice.
Check the command format and set the
number of items correctly.
Check the command data and reenter it
correctly.
Check the data link table file for corruption.
Execute the instruction again after issuing
the PROGRAM AREA PROTECT CLEAR
command to the PC.
Check the file name and either interrupt
servicing or wait for servicing to complete
before re-executing the command.
Set or reset the registered table.
Close open files and re-execute the
command.
---
Check the program number and be sure
that it is set correctly.
Check whether the correct file name was
used.
Check whether the memory contents are
correct and replace if incorrect.
Check the contents of the file. A read error
may have occurred.
Section
7-44
Remedy