Specification - Viessmann AC-Box Installation And Service Instructions For Contractors

Pre-assembled unit for implementing the natural cooling and active cooling functions in conjunction with brine/water heat pumps up to 17 kw
Table of Contents

Advertisement

Specification

Dimensions
Length
Width
Height
Weight
Dry
Permiss. ambient temperature
Operation
Storage and transport
Test pressure
Hydraulic connections
Primary circuit flow/return (AC-Box brine inlet/outlet)
Flow/return, heating/cooling circuit, separate cooling circuit
Connection line, primary circuit from/to the heat pump (brine)
Connection line, secondary circuit from/to the heat pump (heating
water)
Power supply
2-way valves
Power supply (AC operation)
Power consumption
IP rating
3-way diverter valve
Power supply (AC operation)
Power consumption
IP rating
Opening time
Closing time
High efficiency circulation pumps
Power supply (AC operation)
Max. output (per pump)
mm
717
mm
350
mm
973
kg
approx. 80
°C
2 to 30
°C
30 to 60
bar
Max. 4.5
MPa
Max. 0.45
G
1
¼
G
1
¼
G
1
¼
DN
20 (multi connect system)
1/N/PE 230 V/50 Hz
230 V/50 Hz
W
1.5
IP
54
230 V/50 Hz
W
5
IP
20
s
10
s
4
230 V/50 Hz
W
72
Specification
33

Advertisement

Table of Contents
loading

Table of Contents