Bryant 912SC Installation, Start-Up, Operating And Service And Maintenance Instructions page 67

Single stage 4-way multipoise condensing gas furnace
Hide thumbs Also See for 912SC:
Table of Contents

Advertisement

WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect 115vac electrical power before changing speed tap.
(Read following caution before changing taps).
CAUTION
!
UNIT DAMAGE HAZARD
To avoid operating outside the rise range and avoid
component damage:
Refer to the Air Delivery Tables to determine which airflows
and settings are allowed for proper heating airflow. DO NOT
use the highlighted settings for Heating airflow. The
highlighted settings are to be used for Cooling and
Continuous Fan ONLY.
Change these settings as required to maintain proper temperature
rise for Heating and Cooling as described above. To change blower
motor speed selections for heating mode, remove blower motor
lead from control HEAT terminal. See Fig. 40. Select desired
blower motor speed lead from one of the other motor leads and
relocate it/them to HEAT (heating blower tap) terminal(s).
Reconnect original lead on SPARE terminal.
Adjust Blower Off Delay (Heat Mode)
If desired, the main blower off time delay period may be
lengthened or shortened when operating in the heating mode to
provide greater comfort. For position and location of jumpers on
control center, see Fig. 40 and Fig. 73.
The blower off delay has four adjustable settings from 90 sec to
180 sec. See Table 19. To change the blower off delay setting,
move the jumper from one set of pins on the control to the pins
used for the desired blower off delay. Factory blower off delay
setting is 120 sec.
Table 19 – Blower Off Delay Jumper Positions
PINS
1 AND 2
Time (in sec.)
90
Adjust Cooling Airflow
The cooling airflow can be set from the remaining blower speed
taps. Refer to the Air Delivery Tables in these instructions.
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
mid- -point of rise range or slightly above.
Adjust Thermostat Heat Anticipator
Mechanical thermostat: Set thermostat heat anticipator to match
the amp draw of the electrical components in the R- -W circuit.
Accurate amp draw readings can be obtained at the wires normally
connected to thermostat subbase terminals R and W.
thermostat anticipator should NOT be in the circuit while
measuring current.
2 AND 3
3 AND 4
4 AND 5
120
150
180
1. Remove thermostat from subbase or from wall.
2. Connect an amp meter across the R and W subbase termi-
nals or R and W wires at wall.
3. Record amp draw across terminals when furnace is in low
heat and after blower starts.
4. Set heat anticipator on thermostat per thermostat instruc-
tions and install on subbase or wall.
5. Install blower access door.
Electronic thermostat: Set cycle rate for 3 cycles per hr.
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked
in the Start- -up procedure section as part of normal operation.
1. Check Main Limit Switch
This control shuts off combustion system and energizes air- -
circulating blower motor, if furnace overheats. By using this
method to check the temperature limit control, it can be es-
tablished that the limit is functioning properly and that the
limit will operate if there is a restricted return- -air supply or
motor failure. If the limit control does not function during
this test, the cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or
sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re- -light when furnace cools down.
2. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115- -v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115- -v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter
should NOT glow and control diagnostic light flashes a
status code 31. If hot surface igniter glows when inducer
motor is disconnected, shut down furnace immediately.
e. Determine reason low pressure switch did not function
properly and correct condition.
f. Turn off 115- -v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and
turn on 115- -v power.
h. Blower will run for 90 sec before beginning the call for
heat again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/TWIN
terminal. Verify that there is nothing plugged into the PLT
connector. (Note: If there is a jumper connector plugged
into PLT, remove it and discard.) See Fig. 40.
3. Verify that the Blower/Heat Off Delay jumpers are set as
desired. See Fig. 40 and 73.
4. Verify that the blower (lower door in upflow position) and
control ("Main" or upper door in upflow position) doors are
properly installed.
5. Verify that there are no unsealed openings in the blower
shelf or casing.
6. Verify that the Status LED glows. If not, check that the
power supply is energized and that the blower door is
secure. See Fig. 64 to interpret diagnostic codes.
7. Cycle test furnace with room thermostat to be sure that it
operates properly with the room thermostat. Check all
modes including Heat, Cool and Fan.
8. Check
operation
instructions.
The
9. Review Owner's Manual with owner.
10. Attach entire literature packet to furnace.
67
of accessories
per manufacturer's

Advertisement

Table of Contents
loading

Table of Contents