Use the table below to record programmer-defined
settings during the generator set controller setup and
calibration. The controller default settings and ranges
provide guidelines. The table contains all faults with
ranges and time delays including items that do not have
adjustments. Some notices give the programmer a
choice to make them active
programmer-defined settings result when the controller
logic does not allow changes or the values are engine
limited.
Programmer-Defined Settings
Description
Engine Functions
Critically high fuel level
(diesel-powered models only) *
ECM communications loss
ECM diagnostics (multiple
inputs) [
ECM diagnostics (multiple
inputs) [
ECM faults (address conflict)
ECM faults (model mismatch)
Engine over speed
Engine RPM
(manual speed adjust)
Version 3.10.3 or higher
Engine start aid active
Engine under speed
Fuel tank leak *
Fuel tank leak *
High battery voltage
High coolant temperature
High coolant temperature
High fuel level (diesel-powered
models only) *
Loss of fuel
Low battery voltage
Low coolant level *
Low coolant temperature
Low cranking voltage
Low engine oil level *
TT-1757
7/18

Appendix A Programmer-Defined Settings

Not adjustable
Write
Access
Controller Display
Display
Message
SiteTech
Fuel Level Critically
High
ECM Comm Err
Shutdwn
ECM xxxxxx Warning
ECM xxxxxx Shutdwn
ECM Addr Err
Shutdwn
ECM Mismatch
Shutdwn
Eng Speed High
S
Shutdwn
Engine RPM Display
DS
Starting Aid Notice
Eng Speed Low
S
Shutdwn
Fuel Leak Warning
Fuel Leak Shutdwn
Battery High Warning
S
Coolnt Temp High
Warning
Coolnt Temp High
Shutdwn
Fuel Level High
Warning
Loss of fuel
Battery Low Warning
S
Coolant Lvl Low
Shutdwn
Coolant Temp Low
Warning
Lo Crank Vlt Warning
Oil Level Low Warning
SiteTecht software is required for programming the APM402
controller. Contact your local distributor/dealer for assistance.
Note: Inhibit time delay is the time delay period after
crank disconnect.
Note: The engine ECM may limit the crank cycle even if
the controller is set to a longer time period.
GenSet
Mode
Always
Range
Default
Running
Setting
Selection
Stopped
0--100%
95%
0--255
0
A
105--120%
115%
60 Hz:
60 Hz:
1751--1849
1800
A
50Hz:
50 Hz:
1451--1549
1500
A
75--95%
85%
A
110--135%
125%
0--100%
90%
A
80--105%
100%
16_C
Fixed
(60_F)
Fixed
60%
Time
Default
Programmer-
Delay
Time
Range
Delay
Defined
(sec.)
(sec.)
Settings
0--10
5
Fixed
10
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Fixed
10
Not adjustable
0--10
5
(0--30
(0
inhibit)
inhibit)
0--10
5
(0--30
(0
inhibit)
inhibit)
0--10
5
Not adjustable
Fixed
90
Not adjustable
Fixed
5
Not adjustable
0--10
5
(0--30
(0
inhibit)
inhibit)
Fixed
6
Not adjustable
Not adjustable
7