Original Issue Date: 5/18
Model: Generator Sets with APM402 or Decision- -Makerr 3000 Controller
Market: Industrial and Residential/Light Commercial
Subject: GM104661, APM402 Controller Service Replacement Kit
Introduction
The controller service replacement kit is available to
replace a non-functional controller. Use the following
procedure to install the replacement controller. See
Figure 1 for typical controller identification. For features
and operation of the controller, see the operation
manual in the literature kit.
Note: Use the APM402 as a service replacement for the
Decision-Makerr 3000. The personality profile
and configuration file from a Decision-Makerr
3000 can be imported into an APM402, however,
a profile from a APM402 cannot be loaded onto a
Decision-Makerr 3000, even if the original profile
was designed for a Decision-Makerr 3000. Also
Decision-Makerr
replacement for an APM402.
Note: The APM402 controller uses different firmware
than the Decision-Makerr 3000 controller. Do
not attempt to load Decision-Makerr 3000
firmware on an APM402 controller, or vice-versa.
Note: WHEN
REPLACING
3000 CONTROLLERS, FIRMWARE IN OTHER
KOHLER ACCESSORIES SUCH AS RSA II,
RSA
III
AND
CONVERTER NEEDS TO BE UPDATED TO
FUNCTION
converter requires both SNMP firmware update
and a .MIB file update. Monitor III software does
not require any updating; however, the APM402
appears as a Decision-Makerr 3000 in this
software. Use the following accessory firmware
upgrades available for download in the Service
Support section of the Kohler Power Resource
Center:
RSA III firmware version 2.02.0 or higher
D
RSA II firmware version 2.00 or higher
D
Modbus/Ethernet converter firmware and
D
.MIB file released June 2018 or later
INSTALLATION INSTRUCTIONS
3000
is
not
a
DECISION-MAKERr
MODBUS/ETHERNET
PROPERLY. Modbus/Ethernet
1. Mini USB connection
service
Figure 1 APM402 Controller
Note: Do not use this controller replacement installation
instruction for upgrading software.
When replacing the controller, the following data must
be resident for the controller to function. Controller
service replacement kits do not include the three files
installed at the factory. The service technician must
install the three files into the replacement controller.
Application program contains the software that
D
controls system operation. The application file was
preprogrammed in the original controller at the
factory.
Personality profile is specific to the engine and
D
alternator and was preprogrammed in the original
controller at the factory.
A backup disk of the personality profile and
application program is supplied with the literature
packet shipped with the generator set. Typically, the
distributor stores this disk for possible future use such
as controller replacement or other circumstances
requiring a backup.
TT-1757 7/18a
GM65741-
1

Advertisement

loading

Summary of Contents for Kohler TT-1757

  • Page 1 Use the following accessory firmware upgrades available for download in the Service A backup disk of the personality profile and Support section of the Kohler Power Resource application program is supplied with the literature Center: packet shipped with the generator set. Typically, the distributor stores this disk for possible future use such RSA III firmware version 2.02.0 or higher...
  • Page 2: Installation Requirements

    Electrically ground the TP-6701 SiteTecht Software Operation Manual generator set and related equipment and electrical circuits. available from the literature section in Kohler Power Turn off the main circuit breakers of all power sources before Resource Center (KPRC). servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because USB Cable with male USB-A and mini-B connectors.
  • Page 3: Installation Procedure

    TB2 (4-Position) Terminal Block for K1 disconnect the electrical connections. relay outputs. Remove the junction box panels as needed to TB3 (6-Position) Terminal Block for access the wiring. E-stop, remote start contacts, and aux. input Remove the four controller panel screws. connections. TT-1757 7/18...
  • Page 4 8. P23 8-pin connector (RJ45) 9. P21 6-pin connector (for RS-485 communications) Align the controller panel with the mounting Figure 3 Main Circuit Board Connectors holes and install four screws. Replace the junction box panels if previously removed. TT-1757 7/18...
  • Page 5 Wait at least 15 seconds and then power up the unit by using the prime power switch (if Backup disk/drive. Use a PC with SiteTecht equipped) or by reconnecting the battery software to load the data from the user negative (--) terminal. parameter backup disk/drive. TT-1757 7/18...
  • Page 6 Test the functionality of the controller by 6.13 Press the generator set master control AUTO reviewing the menus and observing the system button for startup by remote transfer switch or status lamps. Use the Operation Manual as remote start/stop switch. needed. TT-1757 7/18...
  • Page 7: Appendix A Programmer-Defined Settings

    Not adjustable Shutdwn Low coolant temperature 0--10 Coolant Temp Low 16_C Fixed (0--30 Warning (60_F) inhibit) inhibit) Low cranking voltage Lo Crank Vlt Warning Fixed Fixed Not adjustable Low engine oil level * Oil Level Low Warning Not adjustable TT-1757 7/18...
  • Page 8 Not adjustable Emergency stop Emerg Stop Shutdwn Not adjustable Enclosure temperature: high Enclsr Temp: High 5 (20 Fixed Active Fixed Not adjustable shutdown Shutdwn inhibit) Engine cooldown (delay) active Eng Cooldown Notice Engine start delay active Start Delay Notice TT-1757 7/18...
  • Page 9 2--three phase wye, 3--three phase delta Voltage regulator average VR Volt Adj 108--600 voltage adjustment (Voltage) regulator RegCommLoss Not adjustable communication loss Shutdwn SiteTech Read/Write Display Only Charger Absorption Current 1 – 5 Termination Target (A) TT-1757 7/18...
  • Page 10 12 VDC Incorrect charger output System 24 system voltage may cause irreversible damage to the battery and abnormal out gassing. Charger Temperature Active Inactive Compensation Enable Inactive TT-1757 7/18...
  • Page 11 ] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher). ** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the battery charger operation manual. ST--Short Term, LT--Long Term TT-1757 7/18...
  • Page 12 GM65741--2 APM402 Replacement Kit Instructions TT-1757 Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability.