IndraControl XFE01.1-SY-01 Safety Ex-
tension Module
Free-of-ground design for the XM4 control
NOTICE
Do not use the Safety module XFE01.1-SY-01 with an earth-free setup.
The XM4 control is designed free-of-ground. Also refer to the operating instruc-
tions of the IndraControl XM4, R911345566.
10.5.5 Shielding
NOTICE
Provide sufficient shielding.
The shielding reduces any effects of interferences on the system.
Observe the following when shielding:
Fasten the shielding as extensively as possible
●
Ensure proper contact between connector and terminal
●
Avoid damaging or squeezing conductors
●
Note the wire specifications when connecting the shielding
●
Shield the closest possible to the signal terminal points
●
Route all power cables and data cables in separate cable channels.
11 Commissioning
11.1 General information
The product cannot be operated upon delivery. It has to be parameterized or
programmed.
The documentations providing information on the commissioning and project
configuration are listed in
Due to an earth-free setup, the Safety module
XFE01.1-SY-01 might fail.
Control failure due to insufficient shielding
chapter 1.5 "Related documents" on page
R911376654_Edition 04 Bosch Rexroth AG
27/41
Commissioning
2.