Spare Parts And Accessories; Accessories; Wear Parts; Ambient Conditions - Bosch Rexroth IndraControl XFE01.1-SY-01 Operating Instructions Manual

Safety extension module
Hide thumbs Also See for Rexroth IndraControl XFE01.1-SY-01:
Table of Contents

Advertisement

8/41

Ambient conditions

5 Spare parts and accessories

5.1 Accessories

Type code
XA-CN01
XA-BS11
SUP-M01-ENDHALTER
MICRO SD 1GB
Tab. 5-1: Ordering data for accessories

5.2 Wear parts

The Safety extension module has no wear parts.
6 Ambient conditions
Area of application
Ambient temperature of the
control
Relative humidity
Contamination level
Air pressure and
Operating altitude
Degree of protection
Warning if internal tempera-
ture is low
Switch-off if internal tempera-
ture is low
Warning if internal tempera-
ture is high
Switch-off if internal tempera-
ture is high
Overvoltage category
Protection class
Tab. 6-1: Climatic ambient conditions and characteristics
Bosch Rexroth AG R911376654_Edition 04
IndraControl XFE01.1-SY-01 Safety Ex-
Product description
24 V plug
Bus base module for IndraControl extension
modules
2 pieces of snap-on end brackets for 35 mm
NS 35/7.5 or NS 35/15 carrier plate; width:
9.5 mm
SD card
In operation
Only in interior spaces
+5 °C to +55 °C
10% to 95%, condensing not permitted 10% to 95%, condensing not
2 acc. to DIN EN 61131-2
86 kPa to 106 kPa
(up to 2,000 m above sea level)
IP 20 acc. to DIN EN 60529
≤ 5 °C
≤ 1 °C
≥ 86 °C
≥ 89 °C
II
III, DIN EN 61010-2-201
tension Module
Part number
R911173741
R911173772
R911170685
1070924212
Storage and transport
-40 °C to +85 °C
permitted
2 acc. to DIN EN 61131-2
55 kPa to 106 kPa
(Up to 4,700 m above sea lev-
el)
IP 20 acc. to DIN EN 60529

Advertisement

Table of Contents
loading

Table of Contents