INSTALLATION AND OPERATION MANUAL, GAS FIRED STEAMER,
GAS CONNECTION:
1. The Serial and Rating Plate on the unit indicates the type of gas your unit is equipped to
burn. DO NOT connect to any other gas type.
2. A ¾" NPT line is provided at rear for the connection. Each compartment is equipped with
an internal pressure regulator which is set at 3.5" W.C. manifold pressure for natural gas
and 10" W.C. for propane gas. Use
pressure.
An adequate gas supply is imperative. Undersized or low pressure lines will restrict the volume
of gas required for satisfactory performance. A steady supply pressure, between 6" W.C. and
14" W.C. for natural gas and between 11" W.C. and 14" W.C. for propane gas is
recommended. With all units operating simultaneously, the manifold pressure on all units
should not show any appreciable drop. Fluctuations of more that 25% on natural gas and 10%
on propane gas will create problems, affecting burner operation. Contact your gas company for
correct supply line sizes.
Purge the supply line to clean out any dust, dirt or other foreign matter before connecting the
line to the unit. Use pipe joint compound which is suitable for use with Propane on all threaded
connections. A manual gas shut off valve for each compartment is supplied with the unit.
Test pipe connections thoroughly for gas leaks.
WARNING: Never use an open flame to check for gas leaks. Check
all connections for leaks using soapy water before use.
NOTE: If applicable, the vent from the gas appliance pressure regulator shall be
installed to the outdoors in accordance with local codes or, in the absence of local
codes, with the National Fuel Gas Code, ANSI Z223.1 or the Natural Gas Installation
Code CAN/CGA-B149.1 or the propane installation code, CAN/CGA-B149.2, as
applicable.
MANUAL 1195732 REV0 (11/22/2011)
MODELS RG24-5, SX-34GC, SX-55GC

INSTALLATION

" pipe tap on the burner manifold for checking
c
8
HEAVY DUTY STEAM