Air-Flow Path; Connection; Use; Remote Control - Studer HPSI Series User And Installer Handbook

Sine wave inverter 19''
Table of Contents

Advertisement

STUDER INNOTEC
The place where the inverter is to be mounted
should meet the following requirements :
Out of reach of non authorised persons.
In a dry place with no condensation.
No inflammable material in the same room.
Not directly on top of the batteries.
Adequate ventilation. Keep min. 10 cm
distance to other object

Air-flow path

HPSI
Bottom

Connection

Check the switch (4) is in " OFF " position.
First connect the 230V outlet (6) to the user
device, so as to prevent any possible accidental
contact.
Check the tension and polarity of the
battery !
The tension of the battery should coincide with
that mentioned in the technical characteristics of
the inverter.
Battery connection :
This connection should done be very
carefully observing the polarity in order not
to damage the device.
Check that the connections are fixed correctly.

Use

After connecting the inverter, make sure the
user devices are correctly plugged in and that
there is no possible contact between the " Line
OUT " (6) and a person.
Users' and Installers' Handbook
Top
HPSI V2.0 E
The working device generates high tensions
which could be fatal !
The inverter can be activated by moving the
switch to the " Auto " position. The " on "
indicator -green LED -(3) is illuminated.
If no user device is connected, the LED blinks
after some seconds, which indicates that the
" standby " mode has started. If a user device is
plugged in, the green LED remains illuminated,
indicating the uninterrupted presence of 230V in
the outlet. If you wish to deactivate the standby
mode, put the switch in " Lock " position. The
inverter will be then working continuously.
Warning :
With the "lock" mode, the no load
consumption of the inverter is 15 to 20
times greater !

Remote control

The inverter can be controlled remotely with a
switch (bi-stable) connected to the (5)
connector on the Back side of the device.
The main switch (4) has priority over the
working mode of the device. If the remote
switch is close, the inverter is out of use.
Adjustments

Standby Level (1)

The activation of the inverter, when working in
automatic mode, is dictated by the detection of a
load. With this function, it is possible to adjust
the minimum load detected between 0,3 and 20
Watts. This level is factory adjusted to 2
watts and so no further adjustment will
probably be needed.

Adjustment procedure

Make sure that no device is connected.
Check for the presence of hidden users such as
television, fax, video, ... which often have a
standby mode and remain working even after
being turned off !
Put the switch in " Autom. " position.
Introduce a screw driver N°2 in the adjustment
knob (1) provided.
Turn clockwise
until tight
Wait until the green LED blinks.
page4