Flue Turret/Adaptor Installation - Worcester Greenstar 8000 Life Installation And Maintenance Instructions Manual

Gas fired condensing combi boiler
Hide thumbs Also See for Greenstar 8000 Life:
Table of Contents

Advertisement

Installation
Fig. 51 Condensate connection
Filling the condensate trap
DANGER
Danger to life from poisoning!
If the condensate trap is not filled, poisonous flue gas can escape.
▶ Fill the condensate trap with approx. 250 ml water via the flue pipe.
Fig. 52 filling the condensate trap with water
5.4

Flue turret/adaptor installation

NOTICE
Flue installation
▶ Refer to the Flue Kit Installation instructions provided with your flue
kit to correctly install the flue with this appliance.
▶ Do not exceed the maximum straight length for a horizontal or vertical
flue or a 60mm plume management system (if used) as stated in
chapter 4.4.
Telescopic flue
▶ Cutting the flue to an exact measurement is not required as the
telescopic flue terminal can allow for some adjustment.
40
Apply silicone lubricant to sealing surfaces, to ease assembly of flue
components.
Refer to the manual supplied with the flue kit for complete installation
instructions.
▶ For plume management and effective flue lengths ( chapter 4.4).
Additional notes and reminders:
• Ensure that all cut lengths are square and free from burrs and cutting/
filing debris.
• Ensure that the flue and seals are not damaged.
• The flue is sealed when assembled correctly, the components are
pushed fully home and secured.
• The flue rises from the appliance at an angle of 3° or 52mm per metre
length.
• Support the flue at each flue extension joint and at each change of
direction, use suitable brackets and fittings:
0010018818-003
– Support bracket kit (silver), part number 7 738 112 876
– Flue bracket 100mm, part number: 7 716 191 177.
– Flue brackets 100mm x 6, part number: 7 716 191 178.
– Flue bracket 125mm, part number: 7 716 191 179.
• Ensure the external wall seal is fitted and properly located in the
groove provided on the terminal. This seal must be installed in the
groove unless the flue is extended beyond a gutter or balcony as
shown in the installation instructions.
1,000mm
Fig. 53 Slope for condensate disposal
▶ Remove the three inner flue tube retaining screws [1].
– The inner tube will be held in place in the appliance.
▶ Check the appliance flue seal [2] is correctly seated and apply
silicone grease.
0010033557-001
Fig. 54 Flue turret centre
[D]
87mm
[W] 220mm
▶ Align the flue turret/vertical adaptor to the appliance flue outlet with
flat facing [3] to the rear of the appliance.
The flue turret/adaptor should be pushed straight down, on to the
appliance.
2,000mm
52mm
104mm
1
l l
W a
W
Greenstar 8000 Life – 6720883865 (2021/11)
0010013472-001
D
2
6720806944-84.1Wo