Mains Supply; Electrical Supply; Gas Supply - Worcester Greenstar 8000 Life Installation And Maintenance Instructions Manual

Gas fired condensing combi boiler
Hide thumbs Also See for Greenstar 8000 Life:
Table of Contents

Advertisement

Pre-Installation
External filling loop
1
3
3
2
4
Fig. 8
External filling loop system fill example
[1]
Cold mains inlet pipe
[2]
Stop valve
[3]
Check valve
[4]
Test point
[5]
Hose union
[6]
Central heating flow pipe
4.2

Mains supply

4.2.1

Electrical supply

• Supply: 230V AC - 50 Hz
• This appliance must not be connected to a three phase supply.
• The wiring between the appliance and the electrical supply must
comply with the latest IET wiring regulations that apply to wiring a
fixed appliance for Class 1 equipment.
• The correct type of RCD must be employed where additional
protection is required that is suitable for a low energy DC modulating
pump according to IET wiring regulations.
• External 3A A fuse to BS1362.
• The appliance must be earthed.
• Cable: PVC insulated 0.75mm
90 °C, to BS EN50525.
• Any additional components that are connected to the appliance with
mains electrical supply must not have a separate supply.
• Additional equipment wired to the appliance must comply with the
latest IET wiring regulations.
• Appliance IP rating - IPX4D
4.2.2

Gas supply

• Appliances using Natural Gas (NG) must be connected to a governed
meter.
• Appliances using Liquid Petroleum Gas (LPG) must be connected to
a regulator.
• Installation and connection of the gas supply to the appliance must
be in accordance with the latest version of BS6891.
• Gas pipe sizing should be calculated to ensure no more than the
permitted mbar drop between the meter/governor to the appliance
inlet ( chapter 12.8).
• The meter or regulator and its pipework must be checked, preferably
by the gas supplier. This is to ensure that the equipment is in good
working order and can meet the gas flow and pressure requirements,
in addition to the demand from any other appliance being served.
Pipe sizing (NG & LPG)
Gas pipework:
▶ Gas installation pipework must be designed to ensure the pressure
loss between the meter outlet (NG) or storage and regulator (LPG)
and the inlet to each appliance does not exceed 1mbar (NG) 2.5mbar
(LPG) ( table 16 "Allowed mbar pressure drop").
14
6
5
2
2
(24 x 0.2mm) temperature rated to
Basic pipe sizing calculation
Basic pipe sizing calculation.
▶ This method is only an estimate - for more complex design please
refer to latest version of BS6891 and training given in ACS.
Natural Gas (NG):
Discharge rates for copper tube with 1mbar differential pressure
between the ends for Natural Gas.
Discharge rates for Natural Gas (m
with straight horizontal copper tube
Pipe
length (m)
3
6
9
12
Discharge
3
15
m
/hr
20
25
30
Table 5 Natural Gas (NG)
Natural Gas:
▶ When using this table to estimate the gas flow rate in pipework of a
known length, the effective length will be increased by 0.5m for each
90° elbow and tee fitted and by 0.3m for each 45° bend.
Liquid Petroleum Gas (LPG):
Discharge rates for copper tube with 2.5mbar differential pressure
between the ends for LPG.
Discharge rates for LPG (m
with straight horizontal copper tube
Tubing
length (m)
15mm
3
kW
m
/hr
3
38.4
1.49
6
26.1
1.01
9
20.5
0.79
12
17.9
0.70
15
15.5
0.60
18
13.5
0.53
21
12.9
0.50
24
12.0
0.47
Table 6 Liquid Petroleum Gas (LPG)
Liquid Petroleum Gas (LPG):
▶ When using this table to estimate the Gas flow rate in pipework of a
known length, the effective length will be increased by 0.6m for each
90° elbow or tee and by 0.3m for each 45° bend or straight coupler.
Greenstar 8000 Life – 6720883865 (2021/11)
3
/hr)
Pipe size (mm)
15
22
28
2.9
8.7
18
1.9
5.8
12
1.5
4.6
9.4
1.3
3.9
8
1.1
3.4
7
0.95
2.9
5.9
0.92
2.5
5.2
0.88
2.3
4.7
3
/hr & kW)
Outside diameter
22mm
28mm
3
kW
m
/hr
kW
207
8.01
412
135
5.21
230
108
4.19
215
94
3.62
187
82
3.20
168
74
2.86
145
67
2.58
135
61
2.58
126
35
32
22
17
15
13
11
9.5
8.5
3
m
/hr
15.92
8.86
8.33
7.25
6.51
5.61
5.24
4.87