Air Conditioning Module Options; Important; Application; Duct Work - Bard WG242D Installation Instructions Manual

Combination gas/electric wall-mount with dehumidification
Table of Contents

Advertisement

1
C
C
M
S
T
D
S
T
D
S
T
D
STD =
Standard equipment.
1
CCM Compressor control module has adjustable 30 second to 5 minute delay-on-break
timer. On initial power up, or any time the power is interrupted, the delay-on-make
will be 2 minutes plus 10% of the delay-on-break setting. There is no delay-on-make
during routine operation of the unit. The module also provides the lockout feature (with 1
retry) for high and/or low pressure controls, and a 2 minute timed bypass for low
pressure control.
2
HPC High pressure control is auto reset. Always used with compressor control module (CCM)
which is included. See note
3
LPC Low pressure control is auto reset. Always used with compressor control module (CCM)
which is included. See note
4
LAC Low ambient control permits cooling operation down to 0°F.
During the initial firing of the burners there will probably be some amount of smoke issued to the
circulating air stream as the result of residual oil burning off of the heat exchanger tubes. This oil
is required during the forming process of the stainless steel heat exchanger tubes to facilitate the
bending. OSHA or the National Toxicology Program does not list the oil as a carcinogen. In
vapor form this may be irritating to the eyes or could cause headaches. This is a one time
occurrence, and ventilation of the space may be required depending upon the space being
conditioned.

1. IMPORTANT

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

2. APPLICATION

This is a fan-assisted forced air gas furnace with
electric air conditioning for outdoor installation. A fan-
assisted furnace is equipped with an integral
mechanical means to draw products of combustion
through the combustion chamber and heat exchanger.
The furnace installation must conform with local
building codes and ordinances or, in their absence, with
the National Fuel Gas Code ANSI Z223.1 or CAN/
CGA-B149.1, latest edition, and the National Electrical
Code ANSI/NFPA-7 or CSA C22.1, latest edition. It is
the personal responsibility and obligation of the
purchaser to contact a qualified installer to assure that
installation is adequate and is in conformance with
governing codes and ordinances.
I
Manual 2100-376
Page
6 of 80

AIR CONDITIONING MODULE OPTIONS

2
3
H
P
C
L
P
C
S
T
D
S
T
D
S
T
D
1.
1.
CAUTION
4
F
a
c
o t
y r
n I
t s
l a
e l
L
A
C
C
o
d
e
G
H
I

3. DUCT WORK

The unit is designed for use with or without duct work.
See Warning on Page 10. Flanges are provided for
attaching the supply and return ducts. These
instructions explain the recommended method to install
the air cooled self-contained electric air conditioning
and gas heating unit and the electrical wiring
connections and gas piping to the unit. The refrigerant
system is completely assembled and charged. All
internal wiring is complete.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heating/cooling system should be carefully read before
beginning the installation. Note particularly "Starting
Procedure" and any tags and/or labels attached to the
equipment.
All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.
Refer to Tables later in this Manual for maximum static
pressure available for duct design.
d
F
e i
d l
n I
t s
l a
e l
d
P
a
t r
C
M
A
1 -
6
C
M
A
1 -
8
C
M
A
6 -