Preparation; Preparing The Installation Site; Installation Site Requirements Of The Indoor Unit; Preparing Water Piping - Daikin Altherma EHVH08S18CB Installation Manual

Low temperature split
Hide thumbs Also See for Altherma EHVH08S18CB:
Table of Contents

Advertisement

3 Preparation

3 Remove the screws at the front of the unit.
4 Push on the button on the bottom of the front plate.
5 Remove the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower
part. Watch your fingers, there are sharp edges on the
lower part of the front plate.
1
a~e+h
2
g
f
4
6 Remove the accessories.
a
b
e
f
a
General safety precautions
b
Addendum book for optional equipment
c
Indoor unit installation manual
d
Operation manual
e
Sealing ring for shut-off valve
f
Shut-off valve
g
User interface cover
h
2 screws for fixing the user interface.
7 Reinstall the top panel and the front plate.
Installation manual
4
4
3
c
d
g
h
3
Preparation
3.1

Preparing the installation site

3.1.1
Installation site requirements of the
indoor unit
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~35°C.
▪ Mind the following spacing installation guidelines:
>10
>10
(mm)
3.2

Preparing water piping

NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN  4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.
3.2.1

To check the water volume and flow rate

Minimum water volume
Check that the total water volume in the installation is minimum
10 litre for EHVH/X04+08 and 20 litre for EHVH/X11+16, the internal
water volume of the indoor unit NOT included.
NOTICE
When circulation in each space heating/cooling loop is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions.
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).
See the installer reference guide for more information.
Minimum required flow rate during defrost/backup heater
operation
04+08 models
11+16 models
See the recommended procedure as described in
during commissioning" on
page 18.
EHVH/X04~16S18CB + EHVH/X08~16S26CB
12 l/min
15 l/min
"6.2  Checklist
Daikin Altherma – Low temperature split
4P384971-1E – 2018.02