Preparation; Preparing The Installation Site; Installation Site Requirements Of The Indoor Unit; Preparing Water Piping - Daikin Altherma EHVZ-CB3V Installation Manual

Table of Contents

Advertisement

3 Preparation

3 Remove the screws at the front of the unit.
4 Push on the button on the bottom of the front plate.
5 Remove the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower
part. Watch your fingers, there are sharp edges on the
lower part of the front plate.
1
a~e+i
2
h
f+g
4
6 Remove the accessories.
a
b
e
f
g
a
General safety precautions
b
Addendum book for optional equipment
c
Indoor unit installation manual
d
Operation manual
e
Sealing ring for shut-off valve
f
Shut-off valve with drain/fill point
g
Shut-off valve
h
User interface cover
i
2 screws for fixing the user interface.
7 Reinstall the top panel and the front plate.
Installation manual
4
4
3
c
d
h
i
3
Preparation
3.1

Preparing the installation site

NOTICE
This unit is designed for operation on 2 temperature zones:
▪ underfloor heating in the main zone, this is the zone
with the lowest water temperature,
▪ radiators in the additional zone, this is the zone with
the highest water temperature.
3.1.1
Installation site requirements of the
indoor unit
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~35°C.
▪ Mind the following spacing installation guidelines:
>10
>10
(mm)
NOTICE
When the temperature in multiple rooms is controlled by 1
thermostat, do NOT place a thermostatic valve on the
emitter in the room where the thermostat is installed.
3.2

Preparing water piping

NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN  4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.
3.2.1

To check the water volume and flow rate

Minimum water volume
Check that the total water volume in the installation is minimum
10  litre for EHVZ04+08 and 20  litre for EHVZ16, the internal water
volume of the indoor unit NOT included. Do NOT split up the
minimum water volume over the 2 temperature zones.
It is sufficient to foresee the minimum water volume on the main
zone. In case of underfloor heating, this is easily done by 1 floor
heating loop that never will be closed by a (remotely) controlled
valve.
It is NOT required to foresee the minimum water volume on the
additional zone.
NOTICE
When circulation in each space heating/cooling loop is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.
EHVZ04~16S18CB3V
Daikin Altherma – Low temperature split
4P401672-1E – 2018.02