Appendix A: NFPA Standard-Specific Requirements

The SFP-2402 and SFP-2404 have been designed for use in commercial, industrial, and
institutional applications and meet the requirements for service under the National Fire Protection
Association (NFPA) Standards outlined in this Appendix. The minimum system components
required for compliance with the appropriate NFPA standard are listed below:
SFP-2402/SFP-2404
Contains the main control board, cabinet (backbox and door), main power supply transformer, and
power supply.
Batteries
Refer to "Power Supply Calculations" on page 44, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
A.1 Central Station/Remote Station Transmitter: Connection
to FACP Dry Contacts
The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer's manual for details.
*Note: The Trouble Relay is a
fail-safe relay. With power
applied to the FACP and no
troubles in the panel, the wiring
should be connected to the C
and TRBL contacts as indicated
in the illustration.
B+
B-
B+
B-
B+
B-
B+
ZONE 1 ZONE 2
ZONE 3 ZONE 4
FACP Main Circuit Board
Figure A.1 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
48
Control Panel
Typical Central Station/Remote Station Transmitter Module
B-
C
NC NO
C TRBL NORM
C
NC NO
TROUBLE
ALARM
SUPV
Typical Input Zone Triggers
JP3
SFP-2402 & SFP-2404 Series Manual — P/N 51898:F3 8/6/2014