Maximum Allowable Vent Pipe Length (in ft.
Winter Design
Vent Pipe
Temperatures1
Diameter
°F (°C)
1-1/2 in.
32 to 21
2 in.
(0 to -6)
2-1/2 in
3 in.
1-1/2 in.
2 in.
20 to 1
(-7 to -17)
2-1/2 in.
3 in.
1-1/2 in.
2 in.
0 to -20
(-18 to -29)
2-1/2 in.
3 in.
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2 Poly-Propylene vent pipe (PP) by Duravent and Centrotherm.
3 Vent lengths in table are equivalent length. Consider each elbow as 5ft of linear length.
NOTE - Concentric terminations are the equivalent of 5' and should be considered when measuring pipe length.
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the maximum allowable
intake or exhaust vent length listed in table 5 or which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See FIGURE 29.
For Winter Design Temperatures Modulating High Efficiency Furnace
070
PVC
PP
2
N/A
N/A
11
9
7
N/A
2
2
N/A
N/A
3
1
1
N/A
1
1
N/A
N/A
1
1
1
N/A
1
1
Conditioned
Space
TABLE 9
) Without Insulation In Unconditioned Space
3
Unit Input Size
090
PVC
PP
2
N/A
N/A
14
12
10
N/A
6
6
N/A
N/A
6
4
1
N/A
1
1
N/A
N/A
1
1
1
N/A
1
1
Conditioned
Space
Pipe Insulation
Unconditioned
Space
FIGURE 29
Page 22
110
PVC
PP
PVC
2
N/A
N/A
18
15
N/A
12
N/A
8
8
13
N/A
N/A
8
6
N/A
3
N/A
1
1
N/A
N/A
2
1
N/A
1
N/A
N/A
Exhaust
Pipe
Intake
Pipe
135
PP
2
N/A
13
N/A
2
2
N/A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Signature slp99uh070xv36bSignature slp99uh090xv36cSignature slp99uh090xv48cSignature slp99uh090xv60cSignature slp99uh110xv60cSignature slp99uh135xv60d ... Show all

Table of Contents