ANN-LED Board Layout and Connection to FACP

Figure 2.23 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.7.7 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.

Specifications

Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mA
Standby: 15 mA
Relay Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Operating Temperature: 32
For indoor use in a dry location only
46
ANN-BUS (ID#)
Address DIP switch
FACP
-24 VDC
+24 VDC
Primary ANN-BUS
Figure 2.23 ANN-LED Board Layout and Connection to FACP
o
F to 120
o
o
o
F (0
C to 49
C)
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
ANN-BUS Devices
ANN-LED