Power-Limited Wiring Requirements - Honeywell Fire-Lite Alarms MRP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Installation

2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent to a
releasing circuit (nonpower-limited without supervision kit REL-4.7K)
Power-limited Circuits
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
ground
stud
Figure 2.10 Typical UL Power-limited Wiring Requirements
28
Nonpower-limited Circuits*
(Class 2)
CAC-5X
Deluge - Preaction Control FACP
Power-limited Circuits (Class 2)
CAC-5X
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
Power-limited Wiring Requirements
Power-limited
Circuits
(Class 2)
4XTMF
Nonpower-
limited
Circuit
Power-limited
Circuit
(Class 2)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms mrp-2001eFire-lite alarms mrp-2001c

Table of Contents