Start-Up - Lennox 16ACX Series Unit Information

Table of Contents

Advertisement

4 - Evacuate the system again using procedure
outlined on page 16.
5 - Weigh in refrigerant.

Start-Up

IMPORTANT
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
1 - Rotate fan to check for binding.
2 - Inspect all factory and field-installed wiring for loose
connections.
3 - After evacuation is complete, open the liquid line
and suction line service valves to release the
refrigerant charge (contained in outdoor unit) into
the system.
Start-Up and Performance Checklist
Job Name
Job Location
Installer
Unit Model No.
Nameplate Voltage
Rated Load Ampacity
Maximum Fuse or Circuit Breaker
Electrical Connections Tight?
Indoor Blower RPM
Discharge Pressure
Refrigerant Lines:
Leak Checked?
Service Valves:
Fully Opened?
Voltage With Compressor Operating
Serial No.
Compressor
Indoor Filter clean?
S.P. Drop Over Indoor (Dry)
Vapor Pressure
Properly Insulated?
Caps Tight?
Page 22
4 - Replace the stem caps and tighten as specified in
Operating Service Valves on page 7.
5 - Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until
you have consulted with the power company and
the voltage condition has been corrected.
6 - Set the thermostat for a cooling demand. Turn
on power to the indoor indoor unit and close the
outdoor unit disconnect switch to start the unit.
7 - Recheck voltage while the unit is running. Power
must be within range shown on the nameplate.
8 - Check system for sufficient refrigerant by using
the procedures listed under Start-Up and Charging
Procedures.
9 - Recheck voltage while the unit is running. Power
must be within range shown on the nameplate.
Job no.
City
City
Service Technician
Outdoor Fan
Supply Voltage (Unit Off)
Outdoor Coil Entering Air Temp.
Refrigerant Charge Checked?
Outdoor Fan Checked?
Calibrated?
Date
State
State
Thermostat
Properly Set?
Level?