4
Connections
The electrical connection must be made by a specialist and comply with the regulations in force.
It must conform to standard NF C 15-100.
The wires to be connected to the WB interface will have a maximum section of 2.5 mm². The WB
interface is powered with a 24 V direct current (DC) supply
DC supply
24 Volt supply
The 24 Volt supply can be connected to the points marked 0 and 24 V - - - on the terminal block
(see Figure 2, Ref.1).
The cable must have a minimum section of 1.5 mm².
Consumption: max. 15 W (sensors connected).
NPMWBEN
Revision A.0
Figure 2
WB Interface
WB/4-20mA CONVERTER
USER MANUAL