Download Print this page

Specifications - Johnson Controls S300 Series Hardware Installation

Hide thumbs Also See for S300 Series:

Advertisement

RDR2S-A and I8O4 Hardware Installation
24-10239-596 Rev. D
T
S
ECHNICAL
PECIFICATIONS
The terminal is expected to operate at moderate temperature variation, non-
condensing humidity variation, moderate vibration, and possible dust
contamination.
Item
Input Power
Reader Interface
General Purpose Inputs
Relay Outputs
Red LED/Green LED Outputs
Communications
Certifications
Mounting Specifications
Dimensions
Ambient Temperature
Humidity
Ventilation
1. The RDR2S-A does not support 1-wire Wiegand readers.
2. IMPORTANT: These open collector outputs can be damaged with the use of alternating current (AC) poten-
tials as low as 1VAC. The LED outputs can only be connected to direct current (DC) loads up to 24VDC.
Specification
+12 to +24VDC or 16 to 24VAC at 24W
1
2-wire Wiegand
12VDC, 250mA (typical), 500mA (peak)
Red indicator
Green indicator
Resistive load
1A max. 0-24VDC/VAC, 25VA max.
2
50mA max. 0-24VDC
2 or 3-wire RS-485
FCC, Class B
CE Mark
C-Tick
DIN rail
Flat surface
5.7 H x 5.9 W x 2.2 D inches (14.4 cm x 15.0 cm x 5.5
cm)
32º to 122ºF (0º to 50ºC)
10 to 85% non-condensing
Cabinets require free movement of air over all
exposed surfaces
36
Technical Specifications
(up to 256 bits)

Advertisement

loading

This manual is also suitable for:

S300-din-rdr2saS300-din-i8o4