Determining The Type Of Heater Location Space - Mr. Heater MHVFRD20NGT Operating Instructions And Owner's Manual

Unvented natural gas fired room heater
Table of Contents

Advertisement

DETERMINING THE TYPE OF HEATER LOCATION
SPACE:
Use this method to determine if you have a confined or
unconfined space.
Note: the space includes the room in which you
install heater plus any adjoining rooms with doorless
passageways or ventilation grills between the rooms.
1. Find the volume of the space by multiplying room length
x width x height.
Example: Space size 18ft (length) x 18ft. (width) x 8ft.
(height) = 2592
If additional ventilation to adjoining room is supplied with
grills or openings, add the volume of these rooms to the
total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the
maximum Btu/hr the space can support.
Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =
51.8 or 51,800 (maximum Btu/hr the space
can support)
WARNING: This heater shall not be installed in a
room or space unless the required volume of indoor
combustion air is provided by the method described
in the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code, or applicable local
codes.
Read the following instructions to insure proper fresh air
for this and other fuel-burning appliances in your home.
3. Add the Btu/hr of all the fuel-burning appliances in the
space such as, Vent–free heater, Gas water heater, Gas
furnace, Vented gas heater, Gas fireplace logs, and Other
gas appliances*
*Do not include direct-vent gas appliances. Direct-vent
draws combustion air from the outdoors and vents to
the outdoors.
Example:
Gas water heater
Vent Free Heater +
Total
4. Compare the maximum Btu/hr the space can support
with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the
space can support)
60,000 Btu/hr (Actual amount of Btu/hr used)
The space in the above example is a confined space
because the actual Btu/hr used is more than the
maximum Btu/hr the space can support.
Unvented Natural Gas Vent Free Room Heaters
40,000 Btu/hr
20,000 Btu/hr
=60,000 Btu/hr
You must provide additional fresh air. Your options are
as follows:
A. Rework worksheet, and the space of an adjoining room.
If the extra space provides an unconfined space, remove
door to adjoining room or add ventilation grills between
the rooms. See Ventilation From Inside Building (Fig. 2)
B. Vent room directly to the outdoors. See Ventilation From
Outdoors (Fig. 3).
C. Install a lower Btu/hr heater if lower Btu/hr size makes
room unconfined.
If actual Btu/hr used is less than the maximum Btu/
hr the space can support, the space is an unconfined
space. You will need no additional fresh air ventilation.
VENTILATION AIR
Ventilation from Inside Building
This fresh air would come from an adjoining unconfined
space. When ventilation to an adjoining unconfined space,
you must provide two permanent openings: one within 12"
of the ceiling and one within 12" of the floor on the wall
connecting the two spaces (see options 1 & 2 of figure 2).
You can also remove door into adjoining room (see option3,
fig 2). Follow the National Fuel Gas Code NFPA 54/ ANSI
Z223.1, Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
WARNING: Rework worksheet, adding the space of
the adjoining unconfined space. The combined space
must have enough fresh air to supply all appliance in
both spaces.
Ventilation from Outdoors
If necessary provide extra fresh air by using ventilation grills
or ducts. Connect these items directly to the outdoors or
spaces open to the outdoors. These include attics* and
crawl spaces. Follow the National Fuel Gas Code NFPA
54/ ANSI Z223.1, Section 5.3, Air for Combustion and
Ventilation for required size of ventilation grills or ducts.
Or remove
Ventilation
door into
Gills into
Adjoining
Adjoining
Room -
Room -
Option 3
Option 1
5
Installation Instructions and Owner's Manual
(30.5 cm)12"
Ventilation Gills into Ad-
joining Room - Option 2
12" (30.5 cm)
Figure 2

Advertisement

Table of Contents
loading

Table of Contents