(e) Selection of pipe between outdoor branch pipes for 3-unit combination: Section E in Figure 1
Size of pipe between outdoor branch pipes varies depending on the capacity of outdoor unit which is connected to second branch pipe in the outdoors.
Select it from the following table.
Total capacity of outdoor units connected
to second branch pipe in the outdoors
500
560
615
670
Use C1220T-1/2H material for φ19.05 or larger.

(4) Selection of an outdoor unit side branching pipe set

This branching pipe set will always become necessary when units are used in combination.
(When a unit is used as a standalone installation, it is not required)
Please note
a) In connecting an outdoor unit, please use a pipe conforming to the pipe size specified for outdoor unit connection.
b) Choose a different-diameter pipe joint matching a main pipe size specified in the above section in installing pipes (= main pipes) on the outdoor unit side.
c) Always install branching pipe (for both gas and liquid) in such a manner that they form correct horizontal branch.
Horizontal
Floor surface
Incline branching pipes within
±15°against the floor surface.

(5) Selection of an indoor unit side branching pipe set

(a) Method of selecting a branching pipe set
As an appropriate branching pipe size varies with the connected capacity (total capacity connected
  ●
downstream), determine a size from the following table.
Please note
In connecting an indoor unit with the indoor unit side branching pipe set, please use a pipe
conforming to the pipe size specified for indoor unit connection.
Always install branching pipes (both gas and liquid pipe) either horizontally or vertically.
Floor surface
(b) Header Method
Depending on the number of units connected, connect plugged pipes (to be procured on the installer's part) at a branching point (on the indoor unit connection side).
  ●
For the size of a plugged pipe, please refer to the documentation for a header set (optional part).
  ●
Total capacity downstream
Less than 180
180 or more but less than 371
371 or more but less than 540
540 or more
Please note
a) In connecting a header with an indoor unit, please use a pipe conforming to the pipe size specified for indoor unit connection.
b) In installing a header, always arrange a gas-side header to branch horizontally and a liquid-side header to branch downward.
c) Indoor units 224 and 280 can not be connected to the header.
Gas side
Liquid side
(2) Piping work
Size of pipe between branch pipes
Gas pipe
φ28.58× t 1.0
±15°
Floor surface
Horizontal
Header set model type
Horizontal
Floor surface
downward
branch
Floor surface
Liquid pipe
φ12.7× t 0.8
Floor surface
Floor surface
Floor surface
HEAD4-22-1G
HEAD6-180-1G
HEAD8-371-2
HEAD8-540-3
Floor surface
Floor surface
141
-
-
'14 • KX-SM-204
Outdoor unit
Branching pipe set
For two units (for 450 – 670)
For three units (for 735 – 1000)
Vertical
Floor surface
Total capacity downstream
Branching pipe set
Less than 180
180 or more but less than 371
371 or more but less than 540
540 or more
Number of branches
4 branches at the most
6 branches at the most
8 branches at the most
8 branches at the most
DOS-2A-3
DOS-3A-3
DIS-22-1G
DIS-180-1G
DIS-371-1G
DIS-540-3
Vertical
Floor surface
Floor surface
Floor surface