A.O. Smith DVE-10000 Instruction Manual page 10

Commercial electric water heater
Hide thumbs Also See for DVE-10000:
Table of Contents

Advertisement

MEnus
Most commonly accessed menu. Operating Set Point, Differential settings, Tank Temperature and Tank Probe
Temperatures
Offset are located in this menu.
Current Operating State/Mode (heating/standby etc) and status (open/closed - on/off - yes/no) of monitored
Heater Status
water heater functions and components are displayed in this menu.
Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied
Economy Mode Setup
or reduced demand periods.
The control system's CCB (Central Control Board - see wiring diagrams) features on board SPDT (single pole
double throw) relay contacts for building EMS (Energy Management System) notification of operational conditions
Alarm Output Setup
such as Fault Conditions and heating mode status. This menu features a list of user definable conditions for
relay activation.
Temperature units (°F or °C), appearance (brightness contrast) and backlight delay user adjustable settings are
Display Settings
located in this menu.
Elapsed time of operation, total heating cycle time, heating cycle count, heating element(s) cycle count and on
Heater Information
time along with UIM and CCB software revisions can be viewed in this menu.
Displays any current Alert or Fault messages.
Current Fault/Alert
Retains 9 event history of Fault/Alert messages with time stamp. The Fault History is useful when dealing with
intermittent operational problems or when the customer has reset the control system prior to a service agent's
Fault History
arrival.
Total accumulated number each individual Fault condition has occurred is displayed in this menu. This
Fault Occurrence
running total of Fault Occurrences can be useful in determining which (if any) operational problems have been
persistent.
This control system feature allows the user to restore control system user settings to their factory default settings.
Restore Factory Defaults
Alarm Output Setup and Display Settings menu items ARE NOT changed when factory defaults are restored.
Accessible by pressing the corresponding Operational Button from most menus and screen displays. This menu
Help Menu
provides access to instructions and explanations for user settings, Operating States, Status Icons, manufacturer's
web address, technical support phone number and service agent contact information.
taBlE 3 - Control systEM MEnus
dEsCrIptIon
10