LG CT09F Service Manual page 7

Table of Contents

Advertisement

Part 1 General Information
No ignition sources
No person carrying out work in relation to a refrigeration system which involves
exposing any pipe work that contains or has contained flammable refrigerant
shall use any sources of ignition in such a manner that it may lead to the risk of
fire or explosion. All possible ignition sources, including cigarette smoking,
should be kept sufficiently far away from the site of installation, repairing,
removing and disposal, during which flammable refrigerant can possibly be
released to the surrounding space. Prior to work taking place, the area around
the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. "No Smoking" signs shall be displayed.
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and preferably expel it externally
into the atmosphere.
Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times the manufacturer's maintenance and
service guidelines shall be followed. If in doubt consult the manufacturer's
technical department for assistance.
The following checks shall be applied to installations using flammable
refrigerants:
- The actual refrigerant charge is in accordance with the room size within which
the refrigerant containing parts are installed
- The ventilation machinery and outlets are operating adequately and are not
obstructed
- If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant
- Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected
- Refrigeration pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks
and component inspection procedures. If a fault exists that could compromise safety,
then no electrical supply shall be connected to the circuit until it is satisfactorily dealt
with. If the fault cannot be corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used. This shall be reported to
the owner of the equipment so all parties are advised.
- 7 -
Copyright © 2019 - 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents