Lennox ML196UHE Installation Instructions Manual page 22

Hide thumbs Also See for ML196UHE:
Table of Contents

Advertisement

TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW
EXHAUST
Exhaust
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR
EXHAUST
DIRECT OR NON-DIRECT VENT APPLICATIONS
EXHAUST
INTAKE
2"
2"
3"
* When transitioning up in pipe size, use the shortest length of 2" PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
NON-DIRECT VENT APPLICATIONS
12" max.
2"
or
2"
2"
2"
INTAKE
3"
*2"
EXHAUST
*2"
INTAKE
* When transitioning up in pipe size, use the shortest length of 2" PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
INTAKE
3"
Exhaust
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
Figure 25
(RIGHT HAND DISCHARGE SHOWN)
Exhaust
2"
2"
2"
DO NOT transition
2"
or
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
2"
2"
Exhaust
3"
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
*2"
*2"
Figure 26
Page 22
2"
2"
2"
or
030/045/070 Only
TRANSITION
45°
MAX
SIDE VIEW
030/045/070 Only
1−1/2"
TRANSITION
*2"
*2"
Exhaust
2"
1−1/2"
2"
6" Min
Exhaust
45°
MAX