Connectable components
12.3 PP 72/48D PN 2/2A PN
Control type
The control type must be specified in the Analog Control Byte m+1 (bit 0), so that the 16-bit input
and output values from and to the analog module are correctly interpreted by the control. In the
SINUMERIK ONE control, the value "0" must be entered.
Note
The control type must be set prior to the operating mode so that the first set of user data is not
misinterpreted. In addition to this, the Analog Control Byte m+0 / m+1 must only be accessed
byte by byte.
Assigning parameters to the analog inputs
The analog inputs (AI) can be operated in the following operating modes:
Operating mode 1st channel
No operating mode
Voltage measurement
Current measurement
Temperature measurement (PT100)
Operating mode 2nd channel
No operating mode
Voltage measurement
Current measurement
Temperature measurement (PT100)
Assigning parameters to the analog outputs
The analog outputs (AO) can be operated in the following operating modes:
Operating mode 3rd channel
No operating mode
Voltage output
Current output
Impermissible operating mode
Operating mode 4th channel
No operating mode
Voltage output
Current output
Impermissible operating mode
150
Bit 1
Bit 0
0
0
0
1
1
0
1
1
Bit 3
Bit 2
0
0
0
1
1
0
1
1
Bit 5
Bit 4
0
0
0
1
1
0
1
1
Bit 7
Bit 6
0
0
0
1
1
0
1
1
Equipment Manual, 10/2021, A5E51087503B AA